14 changes: 11 additions & 3 deletions sonic-thermalctld/scripts/thermalctld
Original file line number Diff line number Diff line change
Expand Up @@ -679,7 +679,9 @@ class LiquidCoolingUpdater(threading.Thread, logger.Logger):
leak_start_time = self.leaking_sensors[sensor_name]
profile = sensor.get_leak_profile()
max_minor_secs = profile.get_leak_max_minor_duration_sec() if profile else inf
if max_minor_secs < inf:
# A value of 0 (or negative) means the platform does not support
# time-based escalation from MINOR to CRITICAL; skip escalation.
if 0 < max_minor_secs < inf:
max_minor = leak_start_time + timedelta(seconds=max_minor_secs)
if max_minor <= now:
sensor_leak_severity = LeakSeverity.CRITICAL
Expand Down Expand Up @@ -728,6 +730,9 @@ class LiquidCoolingUpdater(threading.Thread, logger.Logger):
leaking = 'N/A' if not sensor_is_ok else 'Yes' if sensor_is_leak else 'No'
sensor_type = try_get(sensor.get_leak_sensor_type, 'unknown')
sensor_location = try_get(sensor.get_leak_sensor_location, 'unknown')
# Add the timestamp to the leak sensor entry to track when leak occured
# But don't include in fvs_tuple which is used for comparing values
# Hence create a new one fvs_with_ts for updating sesor_table
fvs_tuple = (
('name', sensor_name),
('leaking', leaking),
Expand All @@ -737,10 +742,13 @@ class LiquidCoolingUpdater(threading.Thread, logger.Logger):
('leak_sensor_status', 'Good' if sensor_is_ok else 'Fault'),
('type', str(sensor_type)),
('location', str(sensor_location)),
('leak_severity', str(sensor_leak_severity)),
('leak_severity', sensor_leak_severity.value if sensor_leak_severity is not None else 'None'),
)
if self.last_sensor_fvs.get(sensor_name) != fvs_tuple:
self.sensor_table.set(sensor_name, swsscommon.FieldValuePairs(list(fvs_tuple)))
fvs_with_ts = list(fvs_tuple) + [
('timestamp', now.strftime('%Y%m%d %H:%M:%S')),
]
self.sensor_table.set(sensor_name, swsscommon.FieldValuePairs(fvs_with_ts))
self.last_sensor_fvs[sensor_name] = fvs_tuple

if status == LeakSeverity.CRITICAL and self.last_leak_status != LeakSeverity.CRITICAL:
Expand Down
115 changes: 115 additions & 0 deletions sonic-thermalctld/tests/test_thermalctld.py
Original file line number Diff line number Diff line change
Expand Up @@ -435,6 +435,9 @@ def test_refresh_leak_status_no_leak(self, mock_try_get):
sensor_name, fvp = call[0]
assert sensor_name in ["leakage1", "leakage2"]
assert fvp.fv_dict['leaking'] == 'No'
# timestamp must be present on the initial create write
assert 'timestamp' in fvp.fv_dict
assert fvp.fv_dict['timestamp'] # non-empty

calls_sys = liquid_cooling_updater.system_table.set.call_args_list
for call in calls_sys:
Expand Down Expand Up @@ -555,6 +558,44 @@ def test_refresh_status_with_multiple_leaks(self, mock_try_get):
elif index == 1:
assert fvp.fv_dict['device_leak_status'] == 'CRITICAL'

@mock.patch('thermalctld.try_get')
def test_refresh_status_minor_no_escalation_when_duration_zero(self, mock_try_get):
"""A get_leak_max_minor_duration_sec() value of 0 means the platform does
not support time-based escalation from MINOR to CRITICAL. The severity
must stay MINOR even after the leak has persisted across polls."""
mock_chassis = MockChassis()
mock_chassis.get_liquid_cooling().make_sensor_leak(0)

liquid_cooling_updater = thermalctld.LiquidCoolingUpdater(mock_chassis, 0.5)

sensor = mock_chassis.get_liquid_cooling().leakage_sensors[0]
sensor.get_leak_severity = mock.MagicMock(return_value=LeakSeverity.MINOR)
mock_profile = mock.MagicMock()
mock_profile.get_leak_max_minor_duration_sec = mock.MagicMock(return_value=0)
mock_profile.get_type = mock.MagicMock(return_value='mock_sensor')
sensor.get_leak_profile = mock.MagicMock(return_value=mock_profile)

liquid_cooling_updater.log_error = mock.MagicMock()
liquid_cooling_updater.log_notice = mock.MagicMock()
liquid_cooling_updater.sensor_table = mock.MagicMock()
liquid_cooling_updater.system_table = mock.MagicMock()
liquid_cooling_updater.event_logger = mock.MagicMock()
liquid_cooling_updater.leaking_sensors = {}

mock_try_get.side_effect = lambda func, default: func()

liquid_cooling_updater._refresh_leak_status()
# Poll again after a short delay; even after wall-clock advances, a value
# of 0 must NOT be treated as "immediately escalate".
time.sleep(1.1)
liquid_cooling_updater._refresh_leak_status()

assert liquid_cooling_updater.last_leak_status == LeakSeverity.MINOR
assert "leakage1" not in liquid_cooling_updater.critical_sensors
# No "escalated from MINOR to CRITICAL" error should have been logged.
for call in liquid_cooling_updater.event_logger.log_error.call_args_list:
assert 'escalated from MINOR to CRITICAL' not in call[0][0]

@mock.patch('thermalctld.try_get')
def test_refresh_status_with_long_leak(self, mock_try_get):
"""Test _refresh_leak_status when one sensor leaks for an extended period"""
Expand Down Expand Up @@ -650,6 +691,80 @@ def test_refresh_leak_status_platform_severity_bump(self, mock_try_get):
assert 'CRITICAL leak reported' not in call[0][0]
assert 'escalated from MINOR to CRITICAL' not in call[0][0]

@mock.patch('thermalctld.try_get')
def test_refresh_leak_status_timestamp_on_transitions_only(self, mock_try_get):
"""Timestamp is written on initial create and on real state changes,
but not rewritten on unchanged polls (row is skipped entirely)."""
mock_chassis = MockChassis()
mock_chassis.get_liquid_cooling().make_sensor_leak(0)
liquid_cooling_updater = thermalctld.LiquidCoolingUpdater(mock_chassis, 0.5)

sensor = mock_chassis.get_liquid_cooling().leakage_sensors[0]
sensor.get_leak_severity = mock.MagicMock(return_value=LeakSeverity.MINOR)
# Long max-minor so time-based escalation cannot fire
sensor.get_leak_profile().get_leak_max_minor_duration_sec = mock.MagicMock(return_value=86400)

liquid_cooling_updater.event_logger = mock.MagicMock()
liquid_cooling_updater.sensor_table = mock.MagicMock()
liquid_cooling_updater.system_table = mock.MagicMock()
liquid_cooling_updater.leaking_sensors = {}
liquid_cooling_updater.critical_sensors = set()
liquid_cooling_updater.last_sensor_fvs = {}

mock_try_get.side_effect = lambda func, default: func()

# Cycle 1: initial create — both sensors written, timestamp present
liquid_cooling_updater._refresh_leak_status()
assert liquid_cooling_updater.sensor_table.set.call_count == 2
first_calls = {c[0][0]: dict(c[0][1].fv_dict) for c in
liquid_cooling_updater.sensor_table.set.call_args_list}
assert 'timestamp' in first_calls['leakage1']
ts1_leak1 = first_calls['leakage1']['timestamp']
assert first_calls['leakage1']['leak_severity'] == LeakSeverity.MINOR.value

# Cycle 2: nothing changed — no write at all (diff-gate skips)
liquid_cooling_updater.sensor_table.reset_mock()
liquid_cooling_updater._refresh_leak_status()
assert liquid_cooling_updater.sensor_table.set.call_count == 0, \
"unchanged poll must not rewrite the sensor row"

# Cycle 3: platform escalates severity — write triggers with fresh timestamp
liquid_cooling_updater.sensor_table.reset_mock()
sensor.get_leak_severity = mock.MagicMock(return_value=LeakSeverity.CRITICAL)
# Ensure a distinct timestamp value (strftime resolution = 1s)
import time as _time
_time.sleep(1.1)
liquid_cooling_updater._refresh_leak_status()
# Only the changed sensor (leakage1) is rewritten; leakage2 unchanged
assert liquid_cooling_updater.sensor_table.set.call_count == 1
name, fvp = liquid_cooling_updater.sensor_table.set.call_args_list[0][0]
assert name == 'leakage1'
assert fvp.fv_dict['leak_severity'] == LeakSeverity.CRITICAL.value
assert 'timestamp' in fvp.fv_dict
assert fvp.fv_dict['timestamp'] != ts1_leak1, \
"escalation must record a fresh timestamp"

@mock.patch('thermalctld.try_get')
def test_refresh_leak_status_timestamp_not_in_diff_cache(self, mock_try_get):
"""last_sensor_fvs cache must exclude 'timestamp' so unchanged polls
aren't triggered by the ever-advancing clock."""
mock_chassis = MockChassis()
liquid_cooling_updater = thermalctld.LiquidCoolingUpdater(mock_chassis, 0.5)
liquid_cooling_updater.event_logger = mock.MagicMock()
liquid_cooling_updater.sensor_table = mock.MagicMock()
liquid_cooling_updater.system_table = mock.MagicMock()
liquid_cooling_updater.leaking_sensors = {}
liquid_cooling_updater.critical_sensors = set()
liquid_cooling_updater.last_sensor_fvs = {}

mock_try_get.side_effect = lambda func, default: func()

liquid_cooling_updater._refresh_leak_status()
for sensor_name, cached_tuple in liquid_cooling_updater.last_sensor_fvs.items():
fields = dict(cached_tuple)
assert 'timestamp' not in fields, \
"timestamp must not be in the diff cache for {}".format(sensor_name)

@mock.patch('thermalctld.try_get')
def test_refresh_leak_status_platform_severity_downgrade(self, mock_try_get):
"""Platform downgrades CRITICAL -> MINOR while still leaking.
Expand Down