UNOFFICIAL Home Assistant integration for iNELS central units (ELKO EP) over their ASCII interface — primarily the older CU3-01M and CU3-02M. It talks to the unit directly and needs no Connection Server.
The "IS3" in the name is iNELS3 — the
.is3export format the integration is based on.
It downloads the device list from the export the unit serves itself. It tracks state live: the unit pushes changes on its own, so nothing is polled.
Status: experimental. The protocol is verified against a live unit, the parser against exports from seven installations (17 to 1125 items, IDM3 03-03-34 through 03-05-03). Blinds on a real drive remain unverified — see Limitations.
Without this nothing works — the unit isn't listening on the ASCII port.
In iNELS IDM3 → Central unit configuration → Third part setting:
| Item | What to do |
|---|---|
| Port | Pick a free port. There's no default, so write it down. |
| Separator | Must match the integration's setting. [32] is a space. |
| Number base | Must match the integration's setting. |
| Mode | Remote control + IDM |
On the right, tick the events the unit should send. Whatever you don't tick, the integration will never learn about, and the entity stays stuck at its last value:
Digital_OUT_SwitchOn/SwitchOff— relays (without them you won't catch a switch flip)Analog_OUT_ValueChanged,Analog_OUT_SwitchOn/SwitchOff— dimmersAnalog_IN_ValueChange,Sensor_Change— temperatures, humidities, analog inputsDigital_IN_SwitchOn/SwitchOff— inputs and buttonsSysInt_Change,Program_ValueSwitchOn/Off— system variables
Finally, Save to CU.
How fast state shows up in Home Assistant depends on these checkboxes. The unit is also driven by switches on the walls, so a change need not come from HA — and it's only detected from an event. What has its own event updates within a second or so; what doesn't, only on the periodic re-read (30 s). The variability with changes from the wall (instant vs. 2–3 s) is the unit's own delay before it sends the change over ASCII, not the integration's.
Commands from HA itself show up immediately, and the integration then verifies them by reading back — if the output didn't take, or a switch on the wall flipped it in the meantime, the state corrects itself to reality instead of leaving the icon stuck in the wrong state.
Then Download, restart Home Assistant, and:
Manually: copy custom_components/is3_export into config/custom_components/.
| Field | Description | Default |
|---|---|---|
| Host | The unit's IP address | — |
| ASCII port | from IDM3 (default 1111) |
1111 |
| Export file path | leave empty, it downloads from the unit | empty |
| Separator | from IDM3, offers all 27 options | space [32] |
| Number base | from IDM3 | hexadecimal |
The integration's name is taken from the export header.
No password is entered. The unit's web server serves the export as a static file with no login, so the iNELS project password has no effect on its availability. (If some unit blocks the download anyway, enter the path to a locally downloaded export.)
If entities report an estimated state, your separator or number base is wrong — Home Assistant raises a repair issue to say so. You can correct it without removing the integration: Settings → Devices & services → IS3 Export → ⋮ → Reconfigure.
Settings → Devices & services → IS3 Export → ⋮ → Delete. This closes the
connection and removes every entity and device the integration created. Nothing
is left behind on the central unit — the integration only ever talked to it over
the network — and no files are written outside custom_components/is3_export.
The second byte of the address determines the type:
| Address | Meaning | Entity | Write |
|---|---|---|---|
0x0102 |
relay | switch |
✅ |
0x0104 |
dimmer (with % unit) |
light 0–100 % |
✅ |
0x0203 |
SYSTEMBIT | switch |
✅ |
0x0202 |
SYSTEMINTEGER | number |
✅ |
| address pair | blind | cover |
✅ |
| controller channels | heating zone | climate |
✅ |
0x0101 |
inputs, buttons, controller status outputs | binary_sensor |
❌ |
0x0107 |
module faults | binary_sensor (problem) |
❌ |
0x0105 |
temperature / humidity | sensor |
❌ |
0x0108 |
analog input | sensor |
❌ |
0x0103, 0x0111, 0x0112 |
controller channels | sensor |
❌ |
0x0206 |
water meters, electricity meters | sensor (total) |
❌ |
0x0501, 0x0204, 0x0209, 0x0003 |
plans, groups, schedules | — | ❌ |
Writes happen only where a write is documented. Never to inputs, thermostat channels, or plans.
The hardware ID decides, not the name: anything starting with Controller_
is controller internals and is not written to — a window sensor sits in the same
range as a relay. Conversely, an unnamed relay (_ SA3-04M_RE2_…) is still a
relay.
The address says what the output is; the name says what it's for. A pulse and a lamp are the same as far as the address is concerned.
| In the name | Entity | Icon |
|---|---|---|
imp |
button |
— |
sv |
light |
light bulb |
lamp |
light |
floor lamp |
zrc |
light |
mirror |
LED |
light |
LED strip |
vent |
switch |
fan |
zas |
switch |
socket |
TL (or DIN input) |
event (press + long_press) |
— |
sv, imp, vent, zas, and TL must match as a whole token (otherwise
Svod_vody would be a light and Zastineni a socket); lamp, zrc, and LED
are enough as a prefix.
TL_ (button) makes an event button on any module. A DIN input
is a button on wall controllers and on the central unit itself (In-Out);
on other modules (e.g. the IM3 input module) DIN is a plain binary_sensor
(a maintained contact) until you name it TL_. A wired button distinguishes
both press and long_press (see Wall switches).
A button (imp) sends a pulse on press — the bit to 1 and straight back
to 0. The idle state is always 0, so every next press is again a clean
rising edge that the iNELS program reacts to. (Holding 1 would work only once;
the unit doesn't zero the bit itself.)
It splits on _ and -, and case doesn't matter. The more specific one wins:
imp_sv_chodba is a button.
The light and switch conventions (sv, lamp, zrc, LED, vent, imp)
apply only to physical relays/dimmers and never turn anything into a
writable entity — an input named Sv_okno stays a binary_sensor, and the
system bit blok_noc_lamp stays a switch. Conversely, TL/DIN apply only
to digital inputs (they won't make a button out of a relay).
There are deliberately no more rules. If something comes out differently, override the entity type or icon manually in Home Assistant.
They combine several addresses into one cover entity, from two possible
sources:
- System bits of the blind program — up, down, stop, tilt. The program in the unit drives the contacts itself. It takes priority.
- A pair of JA3 relays — only up and down, stop by releasing both. Used only when there's no program in the export.
Addresses taken by a blind no longer appear as switches.
A heating controller is a set of channels with the same serial suffix plus a
named root <name> Controller_<serial>. Together they form one climate entity:
| Channel | |
|---|---|
| current temperature | Actual-Therm-AOUT |
| target temperature | Required-Therm-AOUT (heating) / Required-Cool-Therm-AOUT (cooling) |
| heats / cools | Required-Heat-DOUT / Required-Cool-DOUT |
| preset | Control-Manual-IN — 0 Schedule, 1–4 Preset 1–4, 7 Manual |
| heating / cooling | Control-HC-IN — 0 heating, 1 cooling |
| on / off | Control-IN — 0 off, 1 on |
The Cool mode is offered for a zone only when it actually has a cooling
output wired. The cooling channels (Control-HC-IN, Required-Cool-*) are
carried by every zone, so their presence isn't enough — the capability is only
recognized from the controller's root row: a heating zone has flags 0x05 with
empty cooling schedule slots, a zone with cooling 0x3F with filled ones
(verified on the unit). Where Cool is available, it's switched via
Control-HC-IN, and cooling has its own setpoints: Required-Cool-Therm-AOUT
(in effect) and Manual-Cool-Therm-AIN (manual).
Setting the temperature switches the zone into Manual and writes
Manual-Therm-AIN (heating), or Manual-Cool-Therm-AIN (cooling). Preset
values 1–4 and the weekly plan behind Schedule (HEATCOOL_WEEK) are set on the
unit.
Watch out for one pitfall (handled): writing the setpoint immediately after switching into Manual corrupts it — the value drops below frost protection (~0.1 °C), and the heating relay with it, and the zone stops heating. So after switching, the integration waits, then writes the setpoint and verifies it by reading back, repeating the write if needed. Manual is value 7, not 5 — a five drops the zone to frost protection.
Each zone also has a select plan — Normal / Vacation / Holiday
(Control-Plan-IN 0 / 64 / 128, all verified on a live unit). Holiday is a
daily program (HEATCOOL_DAY) and must be configured on the unit; where it
isn't, the switch doesn't take and the read-back squares the plan back in the UI.
A single switch breaks down into one entity per channel — nothing is special-cased, it follows from the address type:
| Type | Breakdown into entities |
|---|---|
| WSB3-20 | 8 — 2 buttons (up/down) + 2 LEDs (green/red) + 2 temperatures + 2 digital inputs |
| WSB3-40 | 12 — 4 buttons + 4 LEDs + 2 temperatures + 2 digital inputs |
| WSB3-*-Hum | +2 — humidity (%, device_class humidity) and dew point (°C) |
The indicator LEDs (roles Green/Red) are switches with a G/R
icon — it's recognized from the role, so even unnamed ones (_) get it.
Buttons (Up/Down/DIN) are an event entity. Wired switches (WSB) distinguish
a short press and long_press; the buttons of an RF controller report
only press.
The same recognition applies to the whole family of wall controllers —
besides WSB3, also the glass/touch GSB3, GSP3, MSB3, GBP3, GRT3, the
card readers GMR3/GCR3/GHR3/GCH3, the info panels GDB3, WMR3, and the
room controller IDRT3 (all wired → press+long_press). The RFKEY remote
is all buttons (only press). IBWL (RF input module) is different — each
of its inputs mirrors a paired RF device (a button, but also a door/motion
sensor), which we can't tell from the export, so it's a binary_sensor by
default; to make a particular input a press, name it TL_. A proximity sensor
and a card reader are not treated as buttons.
How short/long works: telling them apart needs the hold duration = the gap
between the close (=1) and the open (=0). On a wired switch this gap is clean
and consistent — taps fall under ~100 ms, deliberate holds over ~1.5 s, with a
wide empty gap in between. So on the close the integration starts a timer: if
the open arrives first, it's a short press; when the timer (1.5 s, the same
as long-press in iNELS) runs out and the button is still held, it's a
long_press — it fires right at that moment, without waiting for release, so
the long-press action kicks in on time. A lost open won't stick the button — a
safety timer releases it.
⚠️ A condition for reliable short/long: no running Connection Server. Its periodic polling freezes the unit for a few seconds and smears the hold duration (see the Connection Server slows the response section below). That originally made this look like a dead end; under clean conditions the timing is reliable.
RF controllers stay on press only — their open is lost too often, and the
hold duration there isn't reliable. For them press fires on every close
event; buttons are meanwhile not deduplicated (the integration normally
wakes an entity only on a value change) so that a lost open doesn't hide the next
press — otherwise the next press would be "no change" and get discarded (hence
the earlier "I have to press 3×"). A short debounce (~0.5 s) swallows only an
immediate double-send of the same press.
Sensors, by contrast, are throttled (max ~1 notification/s) so that a chatty analog input of the CU doesn't flood the loop — the value keeps being stored, only the state isn't written constantly. This keeps button handling snappy.
The RF controller's battery status is a plain binary_sensor (battery), not a
button.
Every physical module (by the serial number in the hardware ID) is its own
device in HA, nested under the central unit. So the channels of one switch,
relay board, or dimmer stay together — you can tell which Green1 belongs to
which switch. System things (bits, integers, buttons) have no module and remain
directly on the central unit.
Hidden by default
Large installations export hundreds of panel internals — button contacts,
indicator LEDs, fault flags. Entities are created from them, but they are
disabled by default. You enable them in the integration settings. Unnamed
ones get their name from the role in the hardware ID (e.g. Up, Green), not
from the whole ID.
Also disabled are the SW status inputs of relays and the fault/alert
flags (OUF-Alert, type 0x0107) — even when they're named, because
hardly anyone watches them. An alert has device_class problem and is
diagnostic.
A device on an RF module (e.g. RFKEY — remotes) appears as its own device with
buttons (binary_sensor), and the Battery_LOW battery status gets
device_class battery.
The export is not a list of everything — in IDM3 you choose what goes into it. If something's missing in Home Assistant, add it there. The integration checks once every 30 minutes whether the list has changed and reloads itself. Reload does it immediately.
Temperatures and humidities come in multiplied by a hundred — 2550 means
25.50 °C. Dimmers are already in percent. SYSTEMINTEGER is a raw value that
isn't converted in any way; what it means is up to the program that uses it.
The ASCII port has no authentication — and the password on the unit won't change that; it only protects the web server. Anyone who reaches that TCP port can control the entire installation.
Keep the unit on a separate VLAN, or at least firewall it off from untrusted devices and from the internet.
- Blinds are not verified on a real drive. For the relay variant, it's
assumed that
1starts the motor and0stops it; the pause when reversing direction is a guess. - Scenes can't be triggered — a
GETon them returnsN, and writing is unverified. - The binary
.otc/.cldformats are not read. They additionally contain named scenes. - Both the HTTP and ASCII ports run without encryption.
If the same central unit is also served by the iNELS Connection Server, expect an occasional delay. The Connection Server reaches into the unit for the complete state roughly every 40–60 s, and during that the unit freezes the entire ASCII output for ~2–4 s — it stops sending events and stops executing commands. Every so often a press or a toggle falls into this window and then reacts those 2–4 s later — and that for all clients at once, including the Connection Server itself (so it delays even itself).
- If you don't need the Connection Server, turn it off — the integration's response is then smooth (the unit answers in ~180 ms).
- If you do need it, slow down / lighten the periodic state polling in its configuration (how often and how much it reads from the unit).
Verified in isolation: the integration itself causes no freezing — it arises only when the Connection Server is also connected.
The number of clients isn't related either: the central unit has a limited number of ASCII connections. Don't point a lot of clients at the ASCII port at once — when the slots run out, the unit will accept the connection but stop serving it (the HTTP export keeps running), and only a CU restart helps.
When something's off, this script finds out what the unit can do — it's
read-only until you add --write:
python tools/probe_is3.py <ip> <port> 0x0102000Apip install -r requirements-test.txt
pytestThe unit also speaks other protocols the integration doesn't work with: ELKONET (binary, port 9999) and XML-RPC on the Connection Server (port 7801) — for that route there's InelsForHass.