InvForge

A fake Modbus TCP inverter/BESS, for testing Modbus-speaking clients (NUT drivers, monitoring tools, anything else) without real hardware. Multi-vendor by design: the Modbus/scenario/control-API engine is vendor-agnostic (invforge/core/), and each vendor's register map, units, and scenario fixtures live in their own profile (invforge/profiles/<vendor>/).

Originally extracted and generalized from a single-vendor Sigenergy simulator built for sigennut; ported here as the first profile (invforge/profiles/sigenergy/) so the same emulator can grow to cover other inverter/BESS families (Deye/SunSynk, Victron GX, Growatt, SolarEdge, ...) as they're needed by the NUT driver work sigennut supports, or other consumers.

Quickstart

python3 -m venv .venv && .venv/bin/pip install -r requirements.txt
.venv/bin/python -m invforge --vendor sigenergy --firmware V100R001C21SPC116 \
    --modbus-port 5020 --control-port 8080 [--scenario <name>]

--firmware can be omitted when a vendor has exactly one confirmed firmware (as Sigenergy does today) — --vendor sigenergy alone resolves to it. Once a second firmware is registered for a vendor, --firmware becomes required and an unknown one exits with a clear list of what's available, rather than silently guessing.

Then point any Modbus TCP client at 127.0.0.1:5020 — same units/register addresses as the real device the profile models. Sigenergy's SigenStor uses unit 247 (plant) and unit 1 (inverter strings).

HTTP control API (port 8080 by default)

The test runner's remote control channel — HTTP+JSON, not gRPC (this is low-throughput, single-consumer, and this way it's curl-able for free while debugging a failed test).

  • GET /health — for Docker healthchecks.
  • GET /scenarios{"library": {name: relative_path, ...}, "generators": [<naming-pattern>, ...]} for the running profile.
  • POST /scenario {"name": "...", "speed": 1.0} — loads and starts playing back a named scenario's timeseries (wall-clock, scaled by speed), looping at its duration. name resolves against the static YAML library first, then the parametric ramp generator (see below) if no library fixture matches. Also clears any forced /fault override back to "auto".
  • POST /fault {"connectivity": "offline"|"online"|"auto"} — on-demand connection-level fault injection: forces the Modbus TCP listener offline/online, or clears back to scenario-driven ("auto"). This drops the real socket (already-connected clients too), not just a register-level Modbus exception. Sticky: takes precedence over a scenario's own offline: windows until cleared or a new scenario is loaded.
  • POST /state {"registers": {"30014": 50, "1:30500": "..."}}instant override: writes directly into the datastore right now and freezes the ticker (mode: "manual") so nothing overwrites it until the next /scenario or /state call. A bare address key targets the profile's default unit; "<unit>:<address>" targets another unit explicitly. Values are raw wire values (bare int for single-register fields, [hi, lo] for S32/U32), same convention as scenario YAML files.
  • GET /state — current raw+decoded value of every known register on every unit, plus current mode/scenario/speed/connectivity — for debugging.

How it works

  • invforge/core/registers.py — vendor-agnostic register model (address/count/dtype/gain/unit/dynamic) plus encode/decode helpers.
  • invforge/core/profile.py — a Profile bundles one vendor+firmware's register list, default unit, and scenario fixtures directory. Register addresses/layouts shift across firmware versions in the real world (see nut-sigenergy/docs/driver-coding-standards.md's note on Sigenergy's own firmware history), so a Profile is scoped to one specific firmware, not a whole vendor — see "Adding a new vendor profile" below.
  • invforge/core/scenario.py — loads a scenario YAML (static / timeseries / exceptions), linearly interpolates numeric registers between consecutive timeseries samples in raw wire-value space.
  • invforge/core/server.py — a pymodbus TCP server with one datastore block per unit id the profile defines. A background thread ticks registers marked dynamic=True forward on a wall-clock timer (--speed multiplier, --tick interval), decoupled from request handling — same as a real device's telemetry loop being independent of what a client happens to poll. Loops back to t=0 once a scenario's duration elapses.
  • invforge/core/generator.py — parametric ramp-scenario generator (see "Parametric ramp scenarios" below); vendor-agnostic mechanism only, a profile supplies the actual ramp-building logic via Profile.ramp_builder.
  • invforge/core/connectivity.py — owns the live Modbus TCP listener's online/offline lifecycle (see "Offline / connection-drop simulation" below).
  • invforge/core/control_api.py — the FastAPI control surface above.
  • invforge/profiles/<vendor>/firmwares/<firmware>/ — a registers.py (the RegisterDef list), a scenarios/ directory, and an __init__.py exporting PROFILE: Profile. See invforge/profiles/sigenergy/firmwares/V100R001C21SPC116/ as the reference example.

Unmapped registers fail Modbus reads the same way a real device would (illegal data address) — a datastore's own address bounds handle this natively for registers never defined at all; a scenario's exceptions: block can mark any other address as always-illegal too, for asserting a client handles a real firmware's odd 400-response quirks correctly.

Some real firmware also rejects specific addresses as a read's starting address specifically — a legitimate, in-range register that simply can't be the first address of a Modbus request, even though a range read starting elsewhere and covering it works fine. Confirmed empirically against real Sigenergy hardware (register 30281). This is a permanent per-firmware trait, not scenario data, so it's modeled separately: Profile.non_anchor_addresses (a frozenset of addresses), enforced by every block regardless of which scenario is loaded. See invforge/profiles/sigenergy/firmwares/V100R001C21SPC116/registers.py's module docstring for the full story.

Sigenergy's own register table is deliberately not the full ~280-entry spec — see that same module docstring for scope (the subset relevant to a UPS/battery-backup driver, matching what the specific real installation this was validated against actually has).

Adding a new vendor profile

  1. Create invforge/profiles/<vendor>/firmwares/<firmware>/registers.py with a REGISTERS: list[RegisterDef] and a DEFAULT_UNIT: int. Use the exact firmware version string as the directory name — this is also what Profile.firmware and --firmware resolve against, no slugifying/casing translation.
  2. Create invforge/profiles/<vendor>/firmwares/<firmware>/__init__.py exporting a module-level PROFILE: Profile (see invforge/profiles/sigenergy/firmwares/V100R001C21SPC116/__init__.py).
  3. Add invforge/profiles/<vendor>/__init__.py exporting a FIRMWARES: dict[str, Profile] (see invforge/profiles/sigenergy/__init__.py), and register it in invforge/profiles/__init__.py's _load().
  4. Add scenarios/recorded/ (real captures, ground truth — validate anything testing against this profile against these before trusting a synthetic scenario) and/or scenarios/synthetic/ (invented ramps, edge cases, bad-data — see below) YAML fixtures under invforge/profiles/<vendor>/firmwares/<firmware>/scenarios/. Since raw register addresses are firmware-specific, scenarios live under the firmware they were captured against/written for, not shared loosely across a vendor's firmware versions — a second firmware with different addresses must not be able to silently misinterpret an old scenario file.
  5. A second confirmed firmware for an existing vendor is a new sibling directory under that vendor's firmwares/, nothing else changes.

Scenario YAML format

static:
  unit_<n>: { <address>: <raw int|word-list|string>, ... }
timeseries:
  - t: <seconds>
    <address>: <raw int|word-list>   # omit a register at a sample to mean
    ...                               # "not sampled here", not "zero" --
                                       # carries forward. Applies to the
                                       # profile's default_unit.
exceptions:
  unit_<n>: { <address>: {function_code: <n>, exception_code: <n>} }
offline:
  - { start: <seconds>, end: <seconds> }   # Modbus TCP is unreachable
    ...                                      # during each [start, end)
                                               # window, elapsed scenario
                                               # time.

All numeric values are RAW wire values (pre-gain), never the decoded real-world value — a bare int for single-register fields, a [hi, lo] word list for multi-register (S32/U32) fields.

Parametric ramp scenarios

For common linear ramps, a scenario name matching linear-<drain|charge>-<start>-to-<end>-<duration>s (e.g. linear-drain-100-to-0-60s) is computed on the fly instead of needing a hand-written YAML file per exact numeric variant — see invforge/core/generator.py. Purely additive to the YAML library: an existing fixture of the same name always wins on a collision. Requires the profile to supply a ramp_builder (see invforge/profiles/sigenergy/firmwares/V100R001C21SPC116/ramps.py for the reference example — it derives ramp power from the rated capacity and requested SoC delta/duration rather than a guessed constant). Invalid ramps (non-positive duration, a drain that doesn't decrease, a charge that doesn't increase) are rejected with ValueError (POST /scenario → HTTP 400).

Offline / connection-drop simulation

A scenario's offline: section (above), or an on-demand POST /fault call, makes the Modbus TCP listener genuinely unreachable for a window — a real dropped/refused connection, not a Modbus-level exception — simulating a device actually going offline (power loss, network outage, Modbus support revoked). See invforge/core/connectivity.py's module docstring for how this is implemented against pymodbus (constructing ModbusTcpServer directly inside its own asyncio loop, since the blocking StartTcpServer convenience wrapper can't be stopped/restarted from outside once running) and why other Modbus exception codes (SlaveBusy, GatewayNoResponse, etc.) aren't reachable through pymodbus's datastore validate() path the way IllegalAddress is.

Bad-data scenarios

A category of scenarios/synthetic/ fixtures that need zero new engine mechanism — just a deliberately out-of-spec static: value, since the engine already writes whatever raw value a YAML gives it. These exist to test whether a driver validates data rather than trusting it blindly: wire-legal register encodings can still decode to values that are physically/semantically impossible (a real firmware bug or a corrupted read could hand a driver exactly this). See invforge/profiles/sigenergy/firmwares/V100R001C21SPC116/scenarios/synthetic/:

  • bad-data-soc-over-100.yamlbattery.charge-equivalent register decodes to 101.0%.
  • bad-data-soh-over-100.yaml — state-of-health register decodes to 150.0%.
  • bad-data-pv-power-negative.yaml — a magnitude-only (generation) power register decodes negative. Chosen over the bidirectional charge/discharge or import/export power registers, where negative is legitimately meaningful by design.

Docker

docker compose up -d --build
curl http://127.0.0.1:8080/health

Maps modbus 5020:502 and control-API 8080:8080 (matching the Quickstart above). The image's ENTRYPOINT is python -m invforge with a CMD giving sane defaults (--vendor sigenergy --firmware V100R001C21SPC116 ...); override vendor/firmware/scenario per the "param via Docker" pattern:

docker run <image> --vendor sigenergy --firmware V100R001C21SPC116 --scenario ramp-discharge-100-to-0

or a command: override in docker-compose.yml. GET /health backs the container HEALTHCHECK.

Testing

  • tests/unit/ — fast, no network: pytest tests/unit -q.
  • tests/integration/ — real Modbus TCP + HTTP against a running instance. One-command local run (build, wait for healthy, run, tear down): scripts/integration-test.sh. In CI (.github/workflows/ci.yml), the same steps run as two jobs (unit, integration) so a lint/type/unit failure fails fast before Docker ever builds.
  • Every push to this repo must pass the invforge-review skill (.claude/skills/invforge-review/) first — see CLAUDE.md.

License

MIT (LICENSE) — this is test tooling, not a sellable artifact; no reason to restrict use.