Reverse-engineered SunSpec Modbus map of the APsystems ECU-C: every register with its implementation status, an undocumented model hidden after the end-of-chain marker, and a silent failure mode that breaks zero export. Probe scripts and Home Assistant config included.

Topics

Resources

Stars

1 star

Watchers

1 watching

Forks

Repository files navigation

APS ECU — SunSpec, local Modbus TCP

apsystems-ecu-sunspec-modbus

GitHub release HACS Custom Validate Home Assistant Installs License: MIT

A Home Assistant integration for the APsystems ECU, talking to the ECU's own SunSpec server over Modbus TCP: no cloud, nothing installed on the ECU. It reads every inverter down to each panel, and exposes the array's power limit and on/off switch, with a zero export blueprint to drive them.

It is built on a register map of the ECU-C measured register by register, which is published here too, with the scripts used to obtain it.

Quick start

  1. On the ECU, in EMA Manager: ECU app, Workspace, Modbus Configuration. Set Switch to On and give every inverter a Modbus address.

  2. Install through HACS, then restart Home Assistant (2026.10 or newer).

    Open in HACS

  3. Add the integration and enter the ECU's IP address. It scans the inverters and shows what it found before creating anything.

    Add integration

  4. Optional: import the zero export blueprint, and paste one of the ready-made dashboards.

    Import blueprint

How it fits together

How the integration fits together

The ECU serves one Modbus unit per inverter on port 502. The integration reads them all through Home Assistant's shared Modbus connection and creates one device per inverter, plus one device for the ECU with the array totals and the controls. The controls act on the whole array: the ECU passes them on to every inverter over Zigbee, which takes about 20 seconds.

Compatibility

Status Notes
ECU-C (ID 215…) ✅ Tested Firmware ECU-C-Z_C1.2.26. APsystems lists Modbus from firmware C1.1.3
ECU-R (ID 2160…) ⚠️ Expected, untested APsystems lists Modbus from firmware 1.3.7
ECU-R Pro (ID 2162…) ⚠️ Expected, untested APsystems lists Modbus from firmware 2.0.2
ECU-B (ID 2163…) ❌ Not possible APsystems disables Modbus on this model
QT2 (three-phase, 4 panels) ✅ Tested Nine QT2-3 on an ECU-C
DS3, DS3-L, DS3-H (single-phase, 2 panels) ⚠️ Simulator only Single-phase models are decoded and tested against a simulated ECU
QS1, YC600, YC1000 ⚠️ Expected, untested Panel count known from the model name
Modbus RTU (RS485) ❌ Not supported TCP only
bolkedebruin/apsystems-sunspec adapter (port 1502) ❌ Not yet Detected and refused with a clear message
Home Assistant 2026.10 or newer Needed for the shared Modbus connection

If you run it on hardware marked ⚠️, an issue saying whether it works, with the integration's diagnostics attached, is very welcome.

Home Assistant integration

Install

HACS, three dots, Custom repositories, add this repository as an Integration, then install APsystems ECU SunSpec (Modbus) and restart Home Assistant. Or copy custom_components/apsystems_ecu_sunspec into your configuration folder.

Home Assistant 2026.10 or newer is required. The integration takes its Modbus connection from Home Assistant's own modbus integration rather than opening its own socket: every integration that addresses the same host and port shares one connection, and their requests queue instead of competing. A second Modbus client has been reported to make an ECU stop answering, so that matters. A modbus: hub declared in YAML still opens a separate connection: do not point one at the ECU while the integration is in use.

Then Settings, Devices & services, Add integration, APsystems ECU SunSpec. Enter the ECU's address. The integration scans the Modbus addresses and shows what it found before creating anything:

  • the inverters that answer, at whatever addresses you gave them in EMA, gaps included;
  • their model and AC topology, single-, split- or three-phase (models 101/102/103 and 111/112/113), per inverter, so a mixed fleet works;
  • the out-of-chain DC block, and how many DC channels each inverter has;
  • which controls of model 123 actually work.

If you add inverters later, use Reconfigure on the integration to scan again.

What you get

One device for the array, one per inverter. Inverters are named after their model and the last 5 digits of their serial number, for example QT2-3 (12345), so the names stay unique with several ECUs and do not depend on the Modbus addresses set in EMA.

Device Entities
APsystems ECU Total AC power, energy produced today, total DC power, inverters producing and online, active events, power limit (number), production and power limit enabled (switches)
APsystems inverter n AC power, current and voltages per phase, frequency, energy produced today, temperature, operating state, events, DC voltage, current and power per channel

The ECU's energy register (WH) counts what each inverter produced today and starts again from zero every day; it is not a lifetime total. The Energy today sensors follow it, and Home Assistant's statistics and Energy dashboard handle the daily reset on their own.

Points the firmware does not implement are not created. Each inverter is read from the integer model (it carries state and events, and its energy counter keeps full precision), with the float model filling any point the integer one leaves empty.

The controls act on the whole array, whichever inverter address they are written through, and are therefore on the ECU device, not on the inverters. Setting a power limit also sets WMaxLim_Ena if it was off, since a limit is otherwise stored and silently ignored. The integration does not run a control loop itself: that is what the blueprint is for.

Zero export blueprint

Zero export control loop

Measured response to power-limit writes

A real test on the ECU-C: the limit stepped to 10, 20, 30 and back to 100 %. Production followed within 7 to 8 seconds; a larger step on another day took about 20 seconds, hence the 30-second control period.

Import blueprint

Or, in Home Assistant: Settings, Automations & scenes, Blueprints, Import blueprint, and paste the raw file address:

https://raw.githubusercontent.com/bdecl/apsystems-ecu-sunspec-modbus/main/blueprints/automation/apsystems_ecu_sunspec/zero_export.yaml

Inputs: a grid power sensor (either sign convention), the power limit entity, the array's rated power, a target grid power, a deadband, separate gains for cutting and releasing, a floor, the control period and an optional enable entity (a tariff or battery-full condition, for instance). It is incremental, holds the last limit when the grid measurement disappears, and puts the array back to 100 % when the enable entity turns off. Keep the period at 30 s or more: dispatch to the inverters takes about 20 s.

Dashboards

Example dashboard, three-phase

homeassistant/dashboards/ has a three-phase and a single-phase dashboard built from native cards only. Paste one into a dashboard's raw configuration editor and copy the per-inverter blocks for each of your inverters.

ECU ID

The ECU itself is not visible over Modbus, so the setup form has an optional ECU ID field: the 12 digits on the ECU label or in EMA. With it, the ECU device is named after its model and the end of its ID, for example ECU-C (1234), and shows its model and serial number. The prefix gives the model, after APsystems' SunSpec Modbus document: 215 ECU-C, 2160 ECU-R, 2162 ECU-R Pro. It can also be added later with Reconfigure.

On a new installation with an ECU ID, the ECU entities are named after the device (sensor.ecu_c_1234_power) instead of sensor.apsystems_ecu_power: adapt the example dashboards. With two ECUs this is what keeps them apart. Adding the ID to an existing entry renames the device, not the entities.

Night and sleeping inverters

When the inverters stop at dusk, the ECU goes on answering with the values of its last round: a few watts, the grid voltage and frequency, operating state MPPT. No register says that the data is old. During the day the ECU refreshes it about every 5 minutes and the measurements change at nearly every round, so an inverter whose measurements have not changed for 15 minutes is shown as asleep: power and currents 0, voltage, frequency and temperature unknown, operating state Sleeping. Energy counters keep their value. It wakes up with the first new data in the morning. Inverters online and Inverters producing count only inverters with fresh data, and each inverter has a Last data update sensor.

After a restart at night the old values show for those first 15 minutes, until the integration has seen that they do not move.

Limits

  • The ECU itself is not visible over Modbus: no ECU serial, no ECU model, and its CT clamps cannot be read. A grid meter has to come from elsewhere.
  • The bolkedebruin/apsystems-sunspec adapter (port 1502, installed on the ECU) is detected but not supported yet.
  • Tested against an ECU-C with QT2 inverters and against a simulator built from the register map. Reports from other ECUs and inverters are welcome.

FAQ and troubleshooting

The power limit does nothing

In order of likelihood:

  • The ECU is linked to an APsystems ELT battery in EMA. The ECU then accepts the limit, reads it back correctly and never applies it, without any error. Remove the link in EMA. Details in docs/elt-link-issue.md.
  • The limit is above what the array is producing. A limit of 50 % changes nothing at 30 % of rated power. Test with a value well below current production.
  • It has not had time yet. The ECU passes the limit on over Zigbee in about 20 seconds. Judge by measured AC power, not by the value read back: the ECU echoes what was written whether it applies it or not.

The integration sets WMaxLim_Ena itself when needed. If you write the registers yourself, 40193 must be 1, or the limit is stored and ignored.

Setup says there is no answer
  • SunSpec must be switched on in EMA (Modbus Configuration, Switch On), and port 502 is fixed.
  • The ECU-B has no Modbus at all.
  • Another Modbus client pointed at the ECU can make it stop answering. Remove any modbus: hub declared in YAML for the ECU: the integration shares Home Assistant's connection with other integrations, but a YAML hub opens its own.
Some inverters are missing

Every inverter needs a Modbus address in EMA, and the scan stops at Highest Modbus address to scan. Raise it if your addresses go higher. After adding inverters or changing addresses in EMA, use Reconfigure on the integration to scan again.

At night the inverters show 0 W and Sleeping

That is expected. The ECU keeps serving the last values it received after the inverters stop, so the integration marks an inverter as asleep when its data has not changed for 15 minutes. See Night and sleeping inverters.

Can I limit or stop a single inverter?

Not over Modbus. The ECU applies model 123 to the whole array, whichever inverter address it is written through. That is why the controls are on the ECU device and not on the inverters.

How do I switch the array off?

With the Production switch on the ECU device. The power limit is not an off switch: even at its lowest setting it lets a small share of rated power through.

The limit keeps jumping up and down

Make sure only one thing writes the limit: a second automation, an older YAML controller or another Home Assistant instance pointed at the same ECU will fight the blueprint. If the blueprint alone oscillates, lower Gain when cutting or lengthen Control period.

The Installs badge shows an error

The count comes from Home Assistant's public usage analytics. It appears once installations with Usage analytics turned on have reported the integration, which takes a day or two after the first ones.

Register map and findings

Everything below was measured on a real installation, not taken from a datasheet. APsystems publishes a short "SunSpec Modbus" document that lists a handful of example reads; it does not say which fields are implemented, and it describes at least one block that is not where the specification says it should be.

Key findings

The immediate controls are global, not per-inverter. Model 123 is read and written through an individual inverter's unit id, but the ECU applies the command to the whole array. Writing Conn = 0 on unit 1 stops every inverter. Writing WMaxLimPct = 1 % on unit 1 curtails the entire installation to 1 % of its rated power. Every other model is genuinely per-inverter. Confirmed on several unit ids.

Model 123 is nearly empty. Of its twenty-four registers, three carry real commands: Conn, WMaxLimPct and WMaxLim_Ena. No power-factor control, no VAr control, and none of the window, revert or ramp timing registers are implemented. Nothing reverts on its own — if your controller stops, the last limit written stays in force indefinitely.

There is an undocumented model after the end of the chain. The SunSpec chain terminates at register 40210. A model 114 header sits at 40212, with 48 registers of per-channel DC data behind it. A conforming client that walks the chain will never see it; it is reachable only by hard-coded address.

The float model loses status. St and Evt1 are implemented in model 103 (integer) and unimplemented in model 113 (float). A client that picks the float model for precision silently loses operating state and event reporting.

The ECU has no meter on Modbus. Unit ids 0 to 247 were scanned: only the configured inverter addresses answer. There is no SunSpec meter model, no reserved unit for the gateway, and nothing in the out-of-chain block that reports grid power. The ECU-C's own CT clamps are not reachable over Modbus by any route.

A silent failure mode breaks zero export entirely. While the ECU is linked to an APsystems ELT storage system in EMA, it accepts power-limit writes, echoes the value back correctly, reports the enable flag as set, and never applies the limit. No error is returned at any layer, and Conn keeps working normally, which makes it look like anything but a suppressed command. See docs/elt-link-issue.md.

Tested on

ECU-C, firmware ECU-C-Z_C1.2.26, nine QT2-3 three-phase microinverters, Modbus TCP on port 502. Identifiers in the documentation are masked.

Other ECU models and firmware versions are likely to differ. If you run the probe scripts on different hardware, a pull request with your output is welcome — that is the point of this repository.

Contents

Path What it is
docs/register-map.md Every register, its type, a measured value and whether the firmware implements it
docs/elt-link-issue.md The silent curtailment failure: symptoms, evidence, diagnosis and fix
docs/official-documentation.md What the manufacturer's reference covers, where it differs from the device, and links
scripts/sunspec_walk.py Walks the model chain and prints what the ECU exposes. Start here
scripts/sunspec_dump.py Full register-by-register dump, emits a markdown table
scripts/ecu_probe.py Scans unit ids and sweeps the address space for undocumented content
custom_components/apsystems_ecu_sunspec Home Assistant integration, installable through HACS
blueprints/automation/apsystems_ecu_sunspec/zero_export.yaml Zero export blueprint for the integration
homeassistant/dashboards/ Ready-made dashboards, three-phase and single-phase
homeassistant/modbus.yaml YAML alternative: Modbus hub and sensors, documented and ready to adapt
homeassistant/zero_export_example.yaml YAML alternative: minimal zero-export controller

Getting started with the scripts

Enable SunSpec on the ECU first: EMA Manager, ECU app, Workspace, Modbus Configuration. Set Switch to On and give each inverter an address. Those addresses become the Modbus unit ids. Port 502 is fixed.

pip install pymodbus
python3 scripts/sunspec_walk.py <ecu-ip> 1

All three scripts are read-only. They never write to the device.

Before you write anything

Read back what you write, but do not trust the readback. The ECU echoes a stored value whether or not it intends to act on it. The only proof that a command took effect is measured AC power.

WMaxLimPct_SF reads -1, so the setpoint is in tenths of a percent: 1000 is 100.0 %. WMaxLim_Ena at 40193 must be 1 or the limit is stored and ignored. Dispatch to the inverters takes about 20 seconds for a large step, so do not run a control loop faster than the array can respond.

And remember that any write into 40186–40209 affects the complete installation, whichever unit id you address.

License

MIT.

About

Reverse-engineered SunSpec Modbus map of the APsystems ECU-C: every register with its implementation status, an undocumented model hidden after the end-of-chain marker, and a silent failure mode that breaks zero export. Probe scripts and Home Assistant config included.