Helios easyControls 3.0 — Home Assistant Integration

HACS custom integration for the Helios KWL easyControls 3.0 ventilation unit. Communication uses the WebSocket protocol on port 80.

Installation

  1. Open the Marketplace (HACS), search for Helios easyControls 3.0 and download it
  2. Restart Home Assistant, then add it under Settings → Devices & services → Add integration → Helios easyControls 3.0
  3. Enter the device's IP address — no credentials required

The integration uses the device serial number for stable unique entity IDs (survive IP changes). If the unit's IP address or hostname changes, use Reconfigure on the entry (three-dot menu) to enter the new one — no need to remove the entry.

Upgrading from v2 or older

v3 changed the integration domain from HeliosEasyControls3_HA to helios_easycontrols3. Home Assistant rejects domains with capital letters: the old one kept the bundled icon from showing and, from Home Assistant 2026.11, kept the Marketplace from installing any update. The Marketplace does not update an installed integration to a new domain, and it refuses to uninstall one while its entry exists, so the old files have to be removed by hand once:

  1. Back up Home Assistant.
  2. Delete the folder custom_components/HeliosEasyControls3_HA, for example in the Terminal app with rm -r /config/custom_components/HeliosEasyControls3_HA or with the File editor app. Do not delete the entry under Settings → Devices & services — that entry is what gets migrated.
  3. Restart Home Assistant. The Marketplace notices the folder is gone and no longer counts the old version as installed; the entry shows as failing until the new version is in place.
  4. Install the integration again from the same repository and restart Home Assistant.
  5. Add it under Settings → Devices & services → Add integration → Helios easyControls 3.0, with the same IP address as before.

Setting it up takes over the old entry with that IP address: the device and all entities move across under their existing entity IDs, so history, dashboards and automations keep working, and the old entry disappears. Step 5 is needed because Home Assistant only starts an integration that has an entry, and the new domain has none until it is added. If the old custom_components/HeliosEasyControls3_HA folder is still present, nothing is migrated and the log asks you to remove it first.


Entities

All entities belong to a single HA device. Within the device card:

  • Main area: operational sensors and controls
  • Konfiguration (EntityCategory.CONFIG): all writable settings
  • Diagnose (EntityCategory.DIAGNOSTIC): device metadata and uptime

Sensors (operational)

Entity Description
Outside / Supply / Indoor / Exhaust Temperature Air temperatures (°C)
Air Relative Humidity Internal humidity sensor (%)
RH Sensor 0–5 External RH sensors, only shown if present
CO2 Sensor 0–5 External CO2 sensors (ppm), only shown if present
VOC Sensor 0–3 External VOC sensors (ppm), only shown if present
Current Fan Speed Current ventilation level (%)
Extract Fan RPM / Supply Fan RPM Actual fan speed (RPM)
Cell State Heat recovery / Cool recovery / Bypass / Defrost
Heat Recovery Efficiency Calculated η = (T_supply − T_outside) / (T_indoor − T_outside)
Intensive / Extra / Individual Mode Timer Remaining Minutes left in active mode
Defrosting Binary: defrost cycle active
Emergency Stop Binary: emergency stop activated
Bypass Status Binary: bypass relay state

Sensors (diagnostic)

Entity Description
Last / Next Filter Change Dates
Filter Remaining Days Days until filter change due
Uptime Years Component / Uptime Hours Component Cumulative device runtime as a pair: whole years, plus the hours on top of them (not a lifetime hour total)
Current Uptime Hours Runtime since last restart
External RH Sensor Count Number of connected external RH sensors
CO2 Sensor Count Number of connected CO2 sensors
VOC Sensor Count Number of connected VOC sensors

Controls

Entity Type Description
(device name) Fan Power, operating mode (presets AtHome / Away / Intensive / Individual) and fan speed of the active mode in one entity — for voice assistants and fan cards. Setting 0 % switches the unit off; the Individual mode's speed is set with its supply/extract numbers
KWL State Select Operating mode: AtHome / Away / Intensive / Individual
On/Off Switch Power the unit on or off

Configuration (Konfiguration)

Entity Type Description
Fan Speed At Home / Away / Intensive Number (%) Target fan speed per profile
Individual Extract / Supply Fan Speed Number (%) Per-fan speed for Individual mode
Extra Extract / Supply Fan Speed Number (%) Per-fan speed for Extra mode
Home / Away / Intensive / Extra / Individual Air Temp Target Number (°C) Supply air temperature target per profile; 5–25 °C as in the device's web UI (Extra has no UI limit and keeps −10–40 °C)
RH Control Home / Away / Intensive Switch Enable humidity-driven fan speed
CO2 Control Home / Away / Intensive Switch Enable CO2-driven fan speed (only shown if CO2 sensor present)
RH Limit Number (%) Global humidity threshold
CO2/VOC Limit Number (ppm) Global CO2/VOC threshold
Intensive Mode Duration Time Duration for boost mode timer
Extra Mode Duration Time Duration for extra mode timer
Individual Mode Duration Time Duration for individual mode timer
Weekly Timer Switch Enable weekly schedule program
Filter Reminder Switch Enable filter change reminder
Temperature Control Mode Select Supply / Extract / Extract+ (Zuluft / Abluft / Abluft Plus)
Heat Exchanger Select Plastic / Enthalpy (cell type)
Bypass Switch Manual bypass enable
Stepless Bypass Switch Stepless (partial) bypass enable
Cool Recovery Switch Activate cool recovery mode

Register Map

Protocol overview

The device uses a proprietary WebSocket binary protocol. A single request (03 00 F6 00 00 00 F9 00) returns all data in one frame. Writes use F9 00 frames with register/value pairs.

Buffer offset formula: buf_offset = group_buf_start + (register − group_reg_start)
Read: data[buf_offset × 2] (high byte), data[buf_offset × 2 + 1] (low byte)
Temperature encoding: kelvin × 100 = round((celsius + 273.15) × 100)

Frame layout — derived from the firmware, not guessed

The web UI bundle defines the reply's structure outright, as RANGE_START_<group> / RANGE_END_<group> constants plus vlxBufferSize=705, which matches the observed frame byte-for-byte. The reply is those ranges concatenated in declaration order:

Group Registers Buf Words
g_cyclone_general_info 0–35 0–35 36
g_typhoon_general_info 256–282 36–62 27
g_cyclone_hw_state 4352–4394 63–105 43
g_cyclone_sw_state 4608–4632 106–130 25
g_cyclone_time 4848–4854 131–137 7
g_cyclone_output 4864–4870 138–144 7
g_cyclone_input 5120–5126 145–151 7
g_cyclone_config 8192–8221 152–181 30
g_cyclone_settings 20480–20555 182–257 76
g_typhoon_settings 21760–21782 258–280 23
g_constant_flow 32768–32783 281–296 16
g_faults 36864–37063 297–496 200
g_cyclone_weekly_schedule 40960–41128 497–665 169
g_cyclone_extended 46000–46038 666–704 39

Two properties of this layout matter when adding registers:

  1. Each range opens with a length marker. The word at a range's nominal start register (always an unnamed address such as 36864 or 40960) holds that range's word count, so the first real value sits at buf_start + 1. Reading A_CYC_TOTAL_FAULT_COUNT at the fault range's start yields 200 — the range length, not a fault count.
  2. Ranges for absent hardware are omitted. g_tornado_0 / g_tornado_1 (45056–45088 / 45216–45248) are declared but missing from this unit's reply, because A_CYC_TOR_0_CONNECTED is 0 — no post-heater module. On a unit that has one, everything after the weekly schedule shifts by 66 words. Anything past the schedule must therefore resolve its offset by walking the length markers rather than hardcoding a position; _find_extended_start() does this.

g_cyclone_hurricane (46100–46113) is declared but is not part of the reply at all. Its registers are reachable only through the second request type below.

Second request type: reading individual registers

WS_WEB_UI_COMMAND_READ_DATA (250) takes a list of addresses instead of dumping the tables, which reaches registers outside the reply frame. The frame is built exactly like a write, with a stride of one word per item:

length_LE(2) + 0xFA00(2) + N×address_LE(2) + checksum_LE(2)
length   = N + 2
checksum = sum of all 16-bit LE words & 0xFFFF

The reply comes back as length + 0xF900 + N×(address, value) + checksum — address/value pairs, so each value is self-identifying. Verified by requesting known registers alongside unknown ones and confirming the known values.

Write frame format:

length_LE(2) + 0xF900(2) + N×(register_LE(2) + value_LE(2)) + checksum_LE(2)
length   = N×4 + 2
checksum = sum of all 16-bit LE words & 0xFFFF

Expected success response: 02 00 F5 00 F7 00

Important: The general info, hardware state, software state and output register ranges (0x0001–0x12F6) are shared with the open-source Vallox WebSocket API. The settings range (0x5000+) differs from the public Vallox layout in places, so the addresses below come from the unit's own firmware rather than from the Vallox API.

Full Vallox API register reference: https://github.com/yozik04/vallox_websocket_api


How the register mapping was obtained

The authoritative source is the unit itself. Its web UI ships the complete register table in clear text, so nothing here needs to be guessed:

  1. Fetch the web UI's bundle. http://<device-ip>/js/bundle.js is served gzip-encoded — decompress it before searching. It contains ~870 VlxDevConstants.<NAME>=<address> assignments, 727 of them A_CYC_*. The extracted table is checked in as docs/registers.json and regenerated with scripts/extract_registers.py.
  2. Find how a control binds to a register. The same bundle defines the UI itself, e.g. coolrecovery:{…data:{value:1,modbus:VlxDevConstants.A_CYC_COOLRECOVERY_DISABLED},list:[{txt:"select_option_off",data:{value:1}},{txt:"select_option_on",data:{value:0}}]}. This gives the register, the value list and any inversion — the three things that are impossible to infer reliably from behaviour alone. Entries named list_helios / helioslist override list on Helios-branded units.
  3. Confirm the read offset. Apply the buffer-offset formula, then check that the value at that offset matches what the UI displays.
  4. Round-trip against the device. Write a changed value, confirm the mapped read offset picks up exactly that value and that the unit's own web UI reflects the change, then restore the original.

Step 4 is what separates a verified mapping from a plausible one. Several bugs in this integration came from correlating a UI reading with a register that was merely being written at the same time. A register that acknowledges a write proves only that the address exists — not that it is the setting you think it is. Both the firmware name and a UI round-trip have to agree before a mapping is recorded as verified here.

A rejected write is silently dropped: the device simply does not send the 02 00 F5 00 F7 00 acknowledgement. Treat a missing ACK as a wrong register or an out-of-range value, never as success.


Group: General Info — buf = reg (reg 1–26)

Reg Hex Buf Name Status Notes
1–10 0x01–0x0A 1–10 A_CYC_APPL_SW_VERSION_0..9 ✅ read Firmware version, shown as the device's software version. Words 2–10 hold one component each, little-endian unlike the rest of the frame; leading zero words dropped, e.g. 1.0.29
11 0x0B 11 A_CYC_BOOT_SW_VERSION ❌ not read Boot SW version
12–13 0x0C–0x0D 12–13 A_CYC_APPL_SW_SIZE_0..1 ❌ not read Application SW size
14 0x0E 14 A_CYC_SERIAL_NUMBER_MSW ✅ read High word of serial number
15 0x0F 15 A_CYC_SERIAL_NUMBER_LSW ✅ read Low word of serial number
16 0x10 16 A_CYC_MACHINE_TYPE ✅ read Device type index (deviceList lookup)
17 0x11 17 A_CYC_MACHINE_MODEL ✅ read Device model index (deviceList lookup)
18 0x12 18 A_CYC_MASTER_PASSWORD ❌ not read —
19–24 — 19–24 A_CYC_CONFIGURATION_* ❌ not read Configuration flags/checksum
26 0x1A 26 A_CYC_NO_HANDEDNESS ❌ not read Device orientation: 0=symmetric, 1=right, 2=left

Group: Hardware State — buf 63, reg 4352 (0x1100)

Reg Hex Buf Name Status Notes
4353 0x1101 64 A_CYC_FAN_SPEED ✅ read Current fan speed % (= CurrentFanSpeed)
4354 0x1102 65 A_CYC_TEMP_EXTRACT_AIR ✅ read Indoor/extract temperature (°C)
4355 0x1103 66 A_CYC_TEMP_EXHAUST_AIR ✅ read Exhaust temperature (°C)
4356 0x1104 67 A_CYC_TEMP_OUTDOOR_AIR ✅ read Outside temperature (°C)
4357 0x1105 68 A_CYC_TEMP_SUPPLY_CELL_AIR ❌ not read Identical to supply air on KWL 360 W ET
4358 0x1106 69 A_CYC_TEMP_SUPPLY_AIR ✅ read Supply air temperature (°C)
4359 0x1107 70 A_CYC_RH_LEVEL ❌ not read Computed RH level (%)
4360 0x1108 71 A_CYC_CO2_LEVEL ❌ not read Computed CO2 level
4361 0x1109 72 A_CYC_EXTR_FAN_SPEED ✅ read Extract fan RPM
4362 0x110A 73 A_CYC_SUPP_FAN_SPEED ✅ read Supply fan RPM
4363 0x110B 74 A_CYC_RH_VALUE ✅ read Relative humidity % (= AirRH)
4364 0x110C 75 A_CYC_CO2_VALUE ❌ not read CO2 value at main sensor
4365 0x110D 76 A_CYC_FIREPLACE_SWITCH ❌ not read Individual mode switch input
4366 0x110E 77 A_CYC_DIGITAL_INPUT ❌ not read Digital input state
4367 0x110F 78 A_CYC_ANALOG_CTRL_INPUT ❌ not read Analog control input
4368 0x1110 79 A_CYC_MULTISENSOR_CO2 ❌ not read Multi-sensor CO2
4369 0x1111 80 A_CYC_MULTISENSOR_TEMP ❌ not read Multi-sensor temperature
4370 0x1112 81 A_CYC_MULTISENSOR_RH ❌ not read Multi-sensor RH
4371 0x1113 82 A_CYC_VOLTAGE_LOW ❌ not read Low voltage flag
4372 0x1114 83 A_CYC_ANALOG_SENSOR_INPUT ❌ not read Analog sensor input
4373–4378 0x1115–0x111A 84–89 A_CYC_RH_SENSOR_0..5 ✅ read External RH sensors (0xFFFF = absent)
4379–4384 0x111B–0x1120 90–95 A_CYC_CO2_SENSOR_0..5 ✅ read External CO2 sensors (0xFFFF = absent)
4385–4388 0x1121–0x1124 96–99 A_CYC_DIP_SWITCH_0..3 ❌ not read DIP switch states
4389 0x1125 100 A_CYC_TEMP_OPTIONAL ❌ not read Optional temperature sensor
4390 0x1126 101 A_CYC_VOC_LEVEL ❌ not read Computed VOC level
4391–4394 0x1127–0x112A 102–105 A_CYC_VOC_SENSOR_0..3 ✅ read External VOC sensors (0xFFFF or 0 = absent)

Group: Software State — buf 106, reg 4608 (0x1200)

Reg Hex Buf Name Status Notes
4609 0x1201 107 A_CYC_STATE ✅ read/write Operating mode (0=AtHome, …)
4610 0x1202 108 A_CYC_MODE ✅ read/write 0=on, ≠0=off
4611 0x1203 109 A_CYC_DEFROSTING ✅ read bool: defrost active
4612 0x1204 110 A_CYC_BOOST_TIMER ✅ read/write Intensive timer remaining (min)
4613 0x1205 111 A_CYC_FIREPLACE_TIMER ✅ read/write Individual timer remaining (min)
4614 0x1206 112 A_CYC_EXTRA_TIMER ✅ read Extra timer remaining (min)
4615 0x1207 113 A_CYC_WEEKLY_TIMER_ENABLED ✅ read/write bool
4616 0x1208 114 A_CYC_CELL_STATE ✅ read 0=HeatRecovery 1=CoolRecovery 2=Bypass 3=Defrost
4617 0x1209 115 A_CYC_TOTAL_UP_TIME_YEARS ✅ read years
4618 0x120A 116 A_CYC_TOTAL_UP_TIME_HOURS ✅ read hours
4619 0x120B 117 A_CYC_CURRENT_UP_TIME_HOURS ✅ read hours
4620 0x120C 118 A_CYC_REMAINING_TIME_FOR_FILTER ✅ read days
4621 0x120D 119 A_CYC_LIMP_MODE ❌ not read Limp mode active
4622 0x120E 120 A_CYC_METRICS ❌ not read Metrics register
4623 0x120F 121 A_CYC_MIN_FAN_START_SPEED ❌ not read Minimum fan start speed
4624 0x1210 122 A_CYC_EMERGENCY_STOP_IS_ACTIVATED ✅ read bool
4625 0x1211 123 A_CYC_DEFROST_SUPERMELT_THRESHOLD ❌ not read Defrost threshold
4626 0x1212 124 A_CYC_ENABLED ❌ not read Device enabled flag
4627 0x1213 125 A_CYC_COMMAND ❌ not read Command register
4628 0x1214 126 A_CYC_MLV_STATE ❌ not read MLV (motor-driven valve) state
4629–4630 — 127–128 A_CYC_UPD_ADDRESS_1..2 ❌ not read Update address
4631 0x1217 129 A_CYC_CLOUD_STATUS ❌ not read Cloud connectivity status
4632 0x1218 130 A_CYC_ANALOG_RH_SENSOR_PRSENT ❌ not read Analog RH sensor present

Group: Time — buf 131, reg 4848 (0x12F0)

Reg Hex Buf Name Status Notes
4848 0x12F0 131 — — Range length marker (7)
4849–4854 0x12F1–0x12F6 132–137 A_CYC_MINUTE / HOUR / DAY / MONTH / YEAR / WEEKDAY ❌ not read Device clock; year is offset from 2000. Decodes correctly against wall-clock time — usable for drift detection

Group: Digital Outputs — buf 138, reg 4864 (0x1300)

buf = 138 + (reg − 4864)

Reg Hex Buf Name Status Notes
4864 0x1300 138 — — Range length marker (7)
4865 0x1301 139 A_CYC_IO_EXTRACT_FAN ✅ read Drive level, not a relay state — observed 135 while the extract fan ran at 1395 rpm
4866 0x1302 140 A_CYC_IO_SUPPLY_FAN ✅ read Drive level; observed 158 at 1638 rpm, tracking the higher supply speed
4867 0x1303 141 A_CYC_IO_ERROR ✅ read bool: error output
4868 0x1304 142 A_CYC_IO_HEATER ✅ read bool: heater output
4869 0x1305 143 A_CYC_IO_EXTRA_HEATER ✅ read bool: extra heater output
4870 0x1306 144 A_CYC_IO_BYPASS ✅ read Bypass relay state (= BypassOpen)

Group: Digital Inputs — buf 145, reg 5120 (0x1400)

Reg Hex Buf Name Status Notes
5120 0x1400 145 — — Range length marker (7)
5121–5126 0x1401–0x1406 146–151 A_CYC_IN_EXTRACT_FAN / SUPPLY_FAN / ERROR / HEATER / EXTRA_HEATER / BYPASS ❌ not read Input states. IN_ERROR reads 1 with no fault present, so the polarity is not plain active-high — do not surface it as a problem flag without clarifying that first

Group: Configuration — buf 152, reg 8192 (0x2000)

Reg Hex Buf Name Status Notes
8192 0x2000 152 — — Range length marker (30)
8194–8195 0x2002–0x2003 154–155 A_CYC_GW_ADDRESS_1..2 ❌ not read Gateway IP, two octets per word
8196–8197 0x2004–0x2005 156–157 A_CYC_MASK_ADDRESS_1..2 ❌ not read Subnet mask
8198–8207 0x2006–0x200F 158–167 A_CYC_HELIOS_*_TUNING ❌ not read Helios-specific DIBT/PHI tuning constants
8211 0x2013 171 A_CYC_ETH_CLOUD_ENABLED ❌ not read Cloud / Ethernet enabled
8212–8213 0x2014–0x2015 172–173 A_CYC_IP_ADDRESS_1..2 ❌ not read Device IP address
8214–8221 0x2016–0x201D 174–181 A_CYC_UUID0..7 ❌ not read Device UUID (8 words)

The address encoding packs two octets per word: 49320 = 0xC0A8 = 192.168, 382 = 0x017E = 1.126. Decoding the block reproduced the unit's actual IP, gateway and mask, which is what confirms these offsets.


Group: Settings — buf 182, reg 20480 (0x5000) — Helios-specific layout

ℹ️ Register names come from the unit's own firmware — see How the register mapping was obtained. The full table is in docs/registers.json.

ℹ️ Profile block layout: each profile occupies four consecutive registers — RH control, CO2 control, fan speed, air temp target — at a stride of 6: Away at 0x5013, Home at 0x5019, Intensive at 0x501F.

Reg Hex Buf Name (Helios-specific) Status Notes
20480 0x5000 182 — — Range length marker (76)
20481 0x5001 183 A_CYC_USED_SETTINGS_VARIABLES ❌ not read Not the temperature control mode — that is 0x5045
20482 0x5002 184 A_CYC_MODBUS_ADDRESS ❌ not read RTU slave address (UI range 1–247)
20483 0x5003 185 A_CYC_MODBUS_BAUD_X100 ❌ not read Baud ÷ 100 — reads 192, i.e. 19200 baud
20484 0x5004 186 A_CYC_MODBUS_FRAME ❌ not read RTU framing
20485 0x5005 187 A_CYC_EXTR_FAN_BALANCE_BASE ✅ read/write Extract side of the fan balance
20486 0x5006 188 A_CYC_SUPP_FAN_BALANCE_BASE ✅ read/write Supply side of the fan balance
20487 0x5007 189 A_CYC_FIREPLACE_EXTR_FAN ✅ read/write Individual extract fan %
20488 0x5008 190 A_CYC_FIREPLACE_SUPP_FAN ✅ read/write Individual supply fan %
20489 0x5009 191 A_CYC_PARTIAL_BYPASS_DISABLED ❌ not read Partial bypass disabled flag
20490 0x500A 192 A_CYC_RH_BASIC_LEVEL ✅ read/write RH Limit %
20491 0x500B 193 A_CYC_CO2_THRESHOLD ✅ read/write CO2/VOC Limit ppm
20492 0x500C 194 A_CYC_EXTRA_ENABLED ✅ read/write Extra mode enabled. Round-trip verified, but the register has no binding in the web UI, so the UI cross-check could not be performed
20493 0x500D 195 A_CYC_EXTRA_AIR_TEMP_TARGET ✅ read/write Extra air temp target (°C)
20494 0x500E 196 A_CYC_EXTRA_EXTR_FAN ✅ read/write Extra extract fan %
20495 0x500F 197 A_CYC_EXTRA_SUPP_FAN ✅ read/write Extra supply fan %
20496 0x5010 198 A_CYC_EXTRA_TIME ✅ read/write Extra mode duration (min)
20497 0x5011 199 A_CYC_FIREPLACE_AIR_TEMP_TARGET ✅ read/write Individual air temp target (°C)
20498 0x5012 200 A_CYC_CF_FAN_SPEED_UNIT ✅ read CF base airflow unit: 0 = l/s, 1 = m³/h, 2 = %; gated with constant-flow support
20499 0x5013 201 A_CYC_AWAY_RH_CTRL_ENABLED ✅ read/write Away RH control (verified)
20500 0x5014 202 A_CYC_AWAY_CO2_CTRL_ENABLED ✅ read/write Away CO2 control
20501 0x5015 203 A_CYC_AWAY_SPEED_SETTING ✅ read Away fan speed %
20502 0x5016 204 A_CYC_AWAY_AIR_TEMP_TARGET ✅ read/write Away air temp target (°C)
20503 0x5017 205 A_CYC_FILTER_REMINDER_DISABLED ✅ read/write Inverted: 1=reminder off
20504 0x5018 206 A_CYC_FILTER_REMINDER_AUTOMATIC_TIME ✅ read/write Automatic filter reminder interval (UI default 14; no UI min/max, entity uses a permissive 1–365)
20505 0x5019 207 A_CYC_HOME_RH_CTRL_ENABLED ✅ read/write Home RH control (verified)
20506 0x501A 208 A_CYC_HOME_CO2_CTRL_ENABLED ✅ read/write Home CO2 control
20507 0x501B 209 A_CYC_HOME_SPEED_SETTING ✅ read AtHome fan speed %
20508 0x501C 210 A_CYC_HOME_AIR_TEMP_TARGET ✅ read/write Home air temp target (°C)
20509 0x501D 211 A_CYC_DEFROST_RPM_LIMIT ❌ not read Defrost fan speed limit
20510 0x501E 212 A_CYC_MAX_FANSPEED_SCALING_EXTRACT ✅ read/write Max extract fan scaling (no UI min/max; entity clamps 1–100)
20511 0x501F 213 A_CYC_BOOST_RH_CTRL_ENABLED ✅ read/write Intensive RH control
20512 0x5020 214 A_CYC_BOOST_CO2_CTRL_ENABLED ✅ read/write Intensive CO2 control
20513 0x5021 215 A_CYC_BOOST_SPEED_SETTING ✅ read Intensive fan speed %
20514 0x5022 216 A_CYC_BOOST_AIR_TEMP_TARGET ✅ read/write Intensive air temp target (°C)
20515 0x5023 217 A_CYC_MAX_FANSPEED_SCALING_SUPPLY ✅ read/write Max supply fan scaling (no UI min/max; entity clamps 1–100)
20516 0x5024 218 A_CYC_COOLRECOVERY_DISABLED ✅ read/write Cool Recovery switch — inverted (1 = off)
20517 0x5025 219 A_CYC_RELAY_MODE ❌ not read Relay configuration — do not write
20518 0x5026 220 A_CYC_DIGITAL_INPUT_1_MODE ❌ not read Digital input configuration — do not write
20519 0x5027 221 A_CYC_DIGITAL_INPUT_2_MODE ❌ not read Digital input configuration — do not write
20520 0x5028 222 A_CYC_ANALOG_INPUT_MODE ❌ not read Analog input configuration — do not write
20521 0x5029 223 A_CYC_MLV_SUPPLY_LOWER_LIMIT ✅ read/write Was mislabelled A_CYC_DEFROST_TEMP_LIMIT here. MLV supply lower limit, UI range 12–25 °C; decodes to a clean 18.0 °C and accepts writes
20522 0x502A 224 A_CYC_SUPPLY_AIR_DEFROST_TEMP ✅ read/write Supply air defrost temperature, UI range 12–20 °C
20523 0x502B 225 A_CYC_MLV_AUTO_MANUAL ❌ not read Was mislabelled A_CYC_DEFROST_HYSTERESIS here. MLV function: 0=automatic, 1=manual
20524 0x502C 226 A_CYC_DEFROST_MODE ❌ not read 0=bypass, 1=fan stop — do not write
20525 0x502D 227 A_CYC_DEFROST_RH_PARAM ❌ not read Defrost parameter — do not write
20526 0x502E 228 A_CYC_DEFROST_TEMP_PARAM ❌ not read Defrost parameter — do not write
20527 0x502F 229 A_CYC_DEFROST_EXH_OFFSET ❌ not read Defrost parameter — do not write
20528 0x5030 230 A_CYC_DEFROST_COMP_LIMIT ❌ not read Defrost parameter — rejects writes
20529 0x5031 231 A_CYC_MLV_SUMMER_SETPOINT ✅ read/write UI range 12–25 °C
20530 0x5032 232 A_CYC_MLV_MODES ❌ not read 0=both, 1=preheating, 2=cooling
20531 0x5033 233 A_CYC_MLV_WINTER_SETPOINT ✅ read/write UI range −10–5 °C
20532–20533 0x5034–0x5035 234–235 A_CYC_MLV_SUMMER_/WINTER_HYSTERESIS ❌ not read —
20534 0x5036 236 A_CYC_WATERHEATER_STORED_I ❌ not read PID integral store, not a temperature
20535 0x5037 237 A_CYC_INSTALLATION_DONE ❌ not read Commissioning flag — do not write
20536 0x5038 238 A_CYC_DEFROST_RH_OFFSET ❌ not read Defrost parameter — do not write
20537 0x5039 239 A_CYC_FILTER_CHANGE_INTERVAL ✅ read Filter interval in days (180 = the UI's "6 months")
20538 0x503A 240 A_CYC_CELL_TYPE ✅ read/write Heat Exchanger select — 0=aluminium (not on Helios) 1=plastic 2=enthalpy
20539–20542 0x503B–0x503E 241–244 A_CYC_EXTRA_HEATER_TYPE / POST_HEATER_TYPE / BRANDING / SIDEDNESS ❌ not read —
20543 0x503F 245 A_CYC_RH_LEVEL_MODE ✅ read/write Humidity mode: 0=automatic, 1=manual
20544 0x5040 246 A_CYC_BOOST_TIME ✅ read/write Intensive mode duration (min)
20545 0x5041 247 A_CYC_FIREPLACE_TIME ✅ read/write Individual mode duration (min)
20546 0x5042 248 A_CYC_FILTER_CHANGED_DAY ✅ read Last filter change day
20547 0x5043 249 A_CYC_FILTER_CHANGED_MONTH ✅ read Last filter change month
20548 0x5044 250 A_CYC_FILTER_CHANGED_YEAR ✅ read Last filter change year (+2000)
20549 0x5045 251 A_CYC_SUPPLY_HEATING_ADJUST_MODE ✅ read/write Temperature Control Mode — 0=supply air 1=extract air 2=cooling mode
20550 0x5046 252 A_CYC_MIN_DEFROST_TIME ❌ not read —
20551 0x5047 253 A_CYC_PARTIAL_BYPASS ✅ read/write Stepless Bypass switch (Helios: 0=off 1=on)
20552 0x5048 254 A_CYC_BYPASS_LOCKED ✅ read/write Bypass switch — inverted (1 = off)
20553 0x5049 255 A_CYC_OPT_TEMP_SENSOR_MODE ❌ not read 0=none, 1=MLV, 2=air heater, 3=supply
20554 0x504A 256 A_CYC_POST_HEATER_WINTER_SETPOINT ✅ read/write UI range 0–19 °C
20555 0x504B 257 A_CYC_DEWPOINT_LIMIT_IN_USE ❌ not read —

Typhoon Settings — buf 258, reg 21760 (0x5500)

⚠️ This range carries credentials in clear text. A_CYC_ACCESS_PASSWORD (buf 260) and A_CYC_USER_PASSWORD (buf 261) are part of every reply. Never expose them as entities or attributes, and redact them from any log or diagnostics dump.

Reg Hex Buf Name Status Notes
21760 0x5500 258 — — Range length marker (23)
21761 0x5501 259 A_CYC_LANGUAGE ❌ not read Display language
21762–21763 0x5502–0x5503 260–261 A_CYC_ACCESS_PASSWORD / USER_PASSWORD 🚫 never expose See warning above
21764–21765 0x5504–0x5505 262–263 A_CYC_ACCESS_LEVEL / PARENTAL_CTRL_ENABLED ❌ not read —
21766 0x5506 264 A_CYC_BOOST_TIMER_ENABLED ❌ not read Boost timer enable
21767 0x5507 265 A_CYC_FIREPLACE_TIMER_ENABLED ❌ not read Individual timer enable
21768–21771 0x5508–0x550B 266–269 A_CYC_SUMMER_TIME_AUTO_ENAB / 12_HOUR_CLOCK / SLEEP_DELAY / BG_LIGHT_LEVEL ❌ not read Panel settings
21772 0x550C 270 A_CYC_EXTRA_TIMER_ENABLED ❌ not read Extra timer enable
21773 0x550D 271 A_CYC_UPDATE_STATUS ❌ not read —

Constant Flow — buf 281, reg 32768 (0x8000)

⚠️ Firmware-dependent. On firmware 1.0.9 the same addresses 0x8001–0x8006 are self-test registers (fans, bypass, heaters), and 0x5012 has no unit meaning. Only 1.0.29 is verified to hold the constant-flow setpoints, so the block is read — and its entities created — only from firmware 1.0.29 on, and only when the range marker at buf 281 reads 16. Later firmware is assumed compatible, not independently verified. Found by @lollo0296 in #7.

The six base airflow numbers follow A_CYC_CF_FAN_SPEED_UNIT (0x5012, buf 200) on each refresh: 0 = l/s, 1 = m³/h, 2 = %. Unknown or unavailable codes have no unit label. Values, write payloads, limits and entity IDs are unchanged; no unit conversion is performed. On 1.0.9 this reserved word can be zero and must not be interpreted as l/s.

Reg Hex Buf Name Status Notes
32768 0x8000 281 — — Range length marker (16)
32769–32774 0x8001–0x8006 282–287 A_CYC_CF_{AWAY,HOME,BOOST}_{SUPPLY,EXTRACT}_BASE_AIRFLOW ✅ read/write Per-profile base airflow; reads 30/30, 50/50, 70/70. No UI min/max, entities use a permissive 0–300
32775–32776 0x8007–0x8008 288–289 A_CYC_MAX_TEST / DUCT_TEST ❌ not read Commissioning tests — do not write
32777–32778 0x8009–0x800A 290–291 A_CYC_MEASURED_SUPPLY / MEASURED_EXTRACT ✅ read Measured airflow; 0 while regulation runs in percent mode
32779–32780 0x800B–0x800C 292–293 A_CYC_CF_LIMITER / CF_LIMITER_ACTIVE ✅ read Limiter state
32781–32782 0x800D–0x800E 294–295 A_CYC_CF_SUPPLY_/EXTRACT_FANLOAD_LEVEL ✅ read Fan load levels

Extended — buf 666, reg 46000 (0xB3B0)

Position shifts when a post-heater module is fitted; resolve it via the range length markers, never by hardcoding 666.

Reg Hex Offset Name Status Notes
46000 0xB3B0 +0 — — Range length marker (39)
46001–46002 0xB3B1–0xB3B2 +1..+2 A_CYC_CONDENSATION_PREVENTION / _METHOD ✅ read —
46003–46004 0xB3B3–0xB3B4 +3..+4 A_CYC_SUPPLY_/EXTRACT_AIRFLOW ✅ read 0 in percent mode
46009 0xB3B9 +9 A_CYC_TOR_0_CONNECTED ✅ read 0 here — this is why the tornado ranges are absent from the reply
46014 0xB3BE +14 A_CYC_CF_FAN_SPEED ✅ read —
46021 0xB3C5 +21 A_CYC_TIMED_FUNCTION_ENABLED ✅ read/write Holiday function on/off
46022–46024 0xB3C6–0xB3C8 +22..+24 A_CYC_TIMED_FUNCTION_START_DAY / MONTH / YEAR ✅ read/write Year offset from 2000; written as one frame so the date stays consistent
46025–46027 0xB3C9–0xB3CB +25..+27 A_CYC_TIMED_FUNCTION_END_DAY / MONTH / YEAR ✅ read/write As above
46028 0xB3CC +28 A_CYC_TIMED_FUNCTION_MODE ✅ read/write 0=at home, 1=away, 2=standby
46029 0xB3CD +29 A_CYC_TIMED_FUNCTION_RETURN_MODE ✅ read No UI binding, so the value list is unknown — exposed read-only
46031–46033 0xB3CF–0xB3D1 +31..+33 A_CYC_CONSTANT_FAN_MAX / MIN / BALANCE ✅ read 200 / 30 / 100
46034 0xB3D2 +34 A_CYC_CONSTANT_AIRFLOW_ALERT ✅ read —

Hurricane — reg 46100–46113 (0xB414–0xB421), not in the reply frame

Reachable only through a READ_DATA request. Probed read-only with known registers alongside for control:

Reg Name Value Notes
46101–46102 A_CYC_MAX_CF_SCALING_SUPPLY / EXTRACT 222 / 222 —
46103–46104 A_CYC_CONSTANT_FAN_P_FACTOR / CF_FUNCTION_CALL_TIME 5 / 5000 —
46105–46106 A_CYC_CF_BLOCKAGE_RATIO_SUPPLY / EXTRACT 400 / 400 —
46107–46108 A_CYC_SUPPLY_/EXTRACT_FILTER_DIRTINESS_INDEX 0 / 0 See below
46109–46113 A_CYC_CF_RECOVERY_* / CF_DUCTCYCLE_* 0 / 55 / 55 / 0 / 0 —

Filter dirtiness index — deliberately not implemented. Both indices read 0 while neighbouring registers in the same block return real values, so the request is not at fault. The index is produced by the constant-flow algorithm, which is not running on this unit: A_CYC_CF_FAN_SPEED_UNIT is 2 (percent regulation), A_CYC_MEASURED_SUPPLY/EXTRACT are 0 and A_CYC_CF_LIMITER_ACTIVE is 0. It would stay 0 until the unit is commissioned for constant-flow regulation, which changes how the whole machine regulates and is not a side effect an integration feature should carry. If that switch is ever made, add it behind a slow second poll — the index moves over weeks.


Faults — buf 297, reg 36864 (0x9000)

Reg Hex Buf Name Status
36864 0x9000 297 — Range length marker (200)
36865 0x9001 298 A_CYC_TOTAL_FAULT_COUNT ❌ not read
36866+ 0x9002+ 299+ A_CYC_FAULT_CODE, SEVERITY, FIRST_DATE, LAST_DATE, COUNT, ACTIVITY (×33) ❌ not read

The whole range reads zero on this unit, so a decode cannot be validated until a fault actually occurs.


Weekly Schedule — buf 497, reg 40960 (0xA000)

168 entries (7 days × 24 hours) at buf 498–665, one word per hour, holding a profile value. Monday 00:00 is buf 498; buf = 498 + day × 24 + hour.

Status Notes
❌ not read/written Present in every reply, so no protocol work would be needed

Implementable next (known registers, just not coded yet)

Register(s) Name Where
buf 26 (reg 26) Device orientation (A_CYC_NO_HANDEDNESS) General info
buf 132–137 Device clock — drift detection against HA's time Time
buf 146–151 Digital input states (clarify IN_ERROR polarity first) Input
buf 154–181 IP / gateway / mask / cloud-enabled as diagnostics Configuration
buf 298+ Fault history Faults
buf 498–665 Full weekly schedule (168 hourly slots) Weekly schedule

An earlier revision of this table listed the IO outputs at buf 144–148. That was wrong: buf 144 is A_CYC_IO_BYPASS, which the integration already read. The outputs are at buf 139–143, and implementing from the old figure would have shifted every one of them by five words.

Pending verification

Item Action needed
Newly writable settings registers Round-trips were verified at register level — write, read back the exact value, restore — but the web UI was not observed during the change. Spot-check fan balance and the post-heater winter setpoint in the unit's own UI to complete step 4 of the methodology
A_CYC_EXTRA_ENABLED (0x500C) Writable and clearly named, but has no binding anywhere in the web UI bundle, so its effect could not be cross-checked
A_CYC_TIMED_FUNCTION_RETURN_MODE (46029) No UI binding, so the value list is unknown; exposed read-only until it is
Fan balance, max fan speed scaling, CF base airflow bounds No min/max in the UI bundle; entity limits are permissive placeholders, not firmware limits
A_CYC_IN_ERROR (buf 148) Reads 1 with no fault present — determine the polarity before surfacing it