Geyser Pasteurization

A Home Assistant custom integration that manages Legionella pasteurization/disinfection cycles for a hybrid hot water (geyser) system — designed for setups where solar PV diversion causes irregular, sometimes-too-low water temperatures that let bacteria proliferate.

It watches a temperature sensor over a rolling window, and if the water hasn't reliably reached and held a safe disinfection temperature, it automatically (or manually) engages a heater entity, holds it at temperature for a required duration, and logs the result — with a hard failsafe timeout so it can never run away.

Why this exists

Hybrid geysers with solar diversion heat opportunistically: whenever there's excess PV, the electric element kicks in, and whenever there isn't, the gas backup or a lower thermostat setpoint takes over. That's great for cost, but Legionella pneumophila can proliferate in water that hovers in the 20–45°C range for extended periods. Municipal/plumbing-code guidance is typically to periodically raise stored water to ~60°C for a sustained period to kill it off. This integration automates that check and, when needed, the disinfection cycle itself — without requiring the geyser to run hot all the time.

Features

  • Rolling-window compliance tracking (default 7 days) against a configurable target temperature and hold duration (default 60°C for 32 minutes), on a fixed schedule that never drifts — see Fixed due schedule below
  • Hotter water counts for more: a time–temperature table (default 60°C/32 min, 65°C/2 min, 70°C/1 min) gives proportional credit for time spent at higher temperatures — see Time–temperature hold table below
  • Recognizes disinfection that happens on its own (e.g. solar diversion reaching target) and won't redundantly run its own active cycle on top of it — see Passive / solar-driven pasteurization below
  • Automatic cycle start when due (optionally restricted to a time-of-day window, e.g. only run overnight), plus a manual trigger button/service
  • A hard failsafe run-time cutoff (default 180 minutes) that disengages the heater and raises an error state if a cycle can't complete
  • Configurable strictness for what happens if temperature dips below target mid-cycle: pause-and-resume (default) or reset-to-zero
  • Survives Home Assistant restarts safely — the last successful cycle timestamp is persisted, but a restart never auto-resumes an in-progress heating cycle
  • Native HA events (geyser_pasteurization_started, geyser_pasteurization_completed, geyser_pasteurization_failed) for automations/notifications
  • Works with switch, input_boolean, climate, or water_heater entities as the heater control
  • Optional grid-power gate for battery/inverter setups: cycles only start (and are paused, not cancelled, mid-cycle) while you're on grid power — see Grid power gate below
  • Fully configurable via the UI (config flow + options flow) — no YAML required

Installation

HACS (custom repository)

  1. In HACS, go to Integrations → ⋮ → Custom repositories.
  2. Add https://github.com/ChrisPotDev/ha-geyser-pasteurization as an Integration.
  3. Install Geyser Pasteurization, then restart Home Assistant.

Manual

  1. Copy custom_components/geyser_pasteurization/ from this repository into your Home Assistant config/custom_components/ directory, so you end up with config/custom_components/geyser_pasteurization/....
  2. Restart Home Assistant.

Add the integration

Settings → Devices & Services → Add Integration → "Geyser Pasteurization", then follow the config flow.

Configuration

All configuration is done through the UI. On initial setup you're asked for:

Field Description Default
Geyser temperature sensor A sensor entity with device_class: temperature reporting the geyser's water temperature —
Heater control entity A switch, input_boolean, climate, or water_heater entity that engages the electric element —
Target disinfection temperature Water must reach/hold this temperature (°C) 60.0
Required continuous duration Minutes the temperature must stay at/above target — the base (slowest) row of the hold table 32
Shorter holds at higher temperatures Extra temperature:minutes rows for the hold table. Leave blank for target/duration only. See Time–temperature hold table. 65:2, 70:1
Maximum rolling window Days without a valid cycle before the system is marked "due" 7
Maximum failsafe run time Safety cutoff — heater is disengaged and the cycle fails if it runs this long without completing 180
Allowed run window (optional) Restricts automatic cycle starts to a time-of-day range (e.g. 02:00–05:00). Manual triggers always bypass this. none (anytime)
Strict cycle reset If a cycle drops below target mid-hold: off pauses the timer and resumes when temp recovers; on resets the timer to zero off
Grid power sensor (optional) Any entity reporting your power source. See Grid power gate. none (always allowed)
"On grid" state value The exact state string of the sensor above that means "on grid power" on

All of these except the two entities can be changed later via Settings → Devices & Services → Geyser Pasteurization → Configure (the options flow), without removing and re-adding the integration.

Time–temperature hold table

Legionella die much faster as the water gets hotter, so a hotter hold needs far less time. The integration doesn't just count minutes at or above the target temperature. It uses a table of equivalent holds. The defaults are commonly cited Legionella kill times: about 32 minutes at 60°C, about 2 minutes at 65°C, and near-instant at 70°C (1 minute is used as a margin). South Africa's SANS 10252-1 only says to store hot water at 55–60°C and gives no hold times, so the 60°C / 32 min base row matches it, and the hotter rows go beyond it. The default table:

At or above Counts as a full pasteurization after
60°C (target temperature) 32 min (required duration)
65°C 2 min
70°C 1 min

The first row is always your configured target temperature and required duration. The extra rows come from the Shorter holds at higher temperatures option, written as 65:2, 70:1. Each extra row must be hotter than the one before it and need less time.

Partial credit adds up across temperatures. Each interval at temperature T adds interval ÷ required time at T to the cycle's progress, and the cycle completes at 100%. Required time is taken from the hottest row the reading reaches, never interpolated, so 63°C counts at the 60°C rate. For example, 10 minutes at 61°C (10/32 ≈ 31%) followed by 1.5 minutes at 66°C (1.5/2 = 75%) completes the cycle. This matters most for solar diversion, which often pushes the tank well above 60°C for a short while. That excursion now counts in full, instead of the integration topping it up with its own heater.

Each interval is credited at the cooler of the readings at its start and end. A rising temperature therefore never earns the faster rate for time before it got there, and the interval in which the tank first crosses the target earns nothing.

sensor.geyser_cycle_progress reports the percentage, and its minutes_remaining attribute estimates the time left at the current temperature. The status and progress sensors both show the active table in a hold_points attribute.

Sensor placement caveat: the reading comes from wherever your sensor sits, usually the thermostat pocket, not the coolest water at the bottom of the tank. A brief spike to 70°C at the sensor doesn't prove the whole tank got there, while a long hold at 60°C is more forgiving of stratification. If you're unsure how well your tank mixes, clear the Shorter holds at higher temperatures field so only the target temperature and duration count.

If you're upgrading from a version without this option, the default 65:2, 70:1 rows apply automatically. If your target temperature or duration isn't the default, any default row that isn't hotter and shorter than your base row is ignored, and a warning is logged.

Fixed due schedule

The next due date is tracked as its own fixed schedule anchor (sensor.geyser_pasteurization_next_due), separate from sensor.geyser_last_pasteurization. Each time a cycle completes, the schedule advances by exactly one rolling-window interval from its own previous scheduled point — never from whenever that particular cycle happened to actually finish. This matters because a cycle's actual completion time varies: an active cycle takes however long it takes to heat and hold, and a passive/solar-driven one might take even longer to naturally reach target. Anchoring the next due date to completion time would let that variance silently drift the schedule later and later, cycle after cycle.

So instead, the due schedule always lands back on the same fixed cadence — e.g. if it first became due at 02:00 on a Monday, it'll next become due at 02:00 the following Monday, regardless of whether that first cycle finished at 02:05 or took until Wednesday to complete passively. If a due date is badly missed (e.g. Home Assistant was offline for a few weeks), it jumps forward in whole window-sized steps to the next future point on that same original schedule, rather than resetting to "now" — so a long outage doesn't shift your schedule either, and you don't get flooded with catch-up cycles for every window that was missed.

Early completions (e.g. solar drives a full valid hold ahead of the current due date — see Passive / solar-driven pasteurization) move the schedule to one rolling window after that completion, so the gap between pasteurizations never exceeds your rolling window. The new due date keeps the schedule's clock time (e.g. 02:00) on the latest such day that is still within the window. For example, if your schedule is 02:00 and solar completes a hold at 18:00 on day 3 of a 7-day window, the next due is 02:00 on day 10 — 6 days 8 hours after the completion, 16 hours short of the full window. Late or on-time completions still advance in whole windows from the existing anchor, so the clock time never drifts.

A manual Reset (button or service) is the one exception: it deliberately re-anchors the schedule to "now + rolling window," since you're explicitly telling the integration to treat this moment as freshly compliant.

Changing the rolling window in Configure takes effect immediately, not just on the next completion. The integration remembers which window size the current schedule point was computed against; if you reconfigure to a different value, it's detected the next time the integration loads (which happens automatically right after you save the change) and the schedule is recomputed from last_pasteurization using the new window straight away — shrinking the window brings the next due date closer, widening it pushes the due date out. A plain restart with no configuration change never triggers this, so it won't unexpectedly reschedule anything on its own.

If you're upgrading from a version without this fixed anchor, it's seeded automatically from your existing last_pasteurization timestamp the first time the integration loads, so your existing cadence continues rather than jumping.

Grid power gate (battery / inverter setups)

If your geyser sits behind a power distribution module that can switch it between grid and inverter/battery (e.g. to protect battery capacity, with automatic failover to inverter on a grid outage), you don't want a disinfection cycle heating off your battery. Set the grid power sensor field to any entity that reflects your current power source — a binary_sensor, switch, input_boolean, or a text/enum sensor (e.g. one reporting "Grid" / "Battery" from a Victron, Deye, Sunsynk, etc. integration) — and set "On grid" state value to whatever that entity reports when you're on grid (defaults to on, which already matches a plain binary_sensor/switch with no changes needed; for a text sensor you'd set this to e.g. Grid). The match is case-insensitive.

If your source is a text/enum sensor and you'd rather not touch the state-value matching, you can instead wrap it in a template binary_sensor helper that's on when on grid, and point the grid power sensor field at that helper with the default on value — either approach works equally well.

With this configured:

  • Due → Heating only happens while on grid power (in addition to the allowed run window, if set).
  • Mid-cycle grid loss (Heating or Pasteurizing) immediately disengages the heater and pauses the cycle — progress toward the required hold duration is preserved, not reset — and it resumes automatically the moment grid power returns, picking up where it left off.
  • Time spent paused waiting for grid power does not count against the failsafe run-time cutoff; only actual heater-engaged time does.
  • The manual trigger button/service also respects this gate and refuses to start a cycle while off-grid (the status sensor's error_message attribute explains why).
  • A binary_sensor.geyser_on_grid_power entity is added automatically once a grid sensor is configured, and the status sensor also exposes on_grid_power and paused_reason attributes for dashboards/automations.

This is handled natively by the integration's own state machine rather than through a separate automation, specifically so that a grid outage mid-cycle pauses and resumes correctly instead of losing progress or needing you to script that logic yourself.

Passive / solar-driven pasteurization

Hold-time toward the required duration is tracked purely from the temperature sensor reading — not from whether this integration's heater is currently switched on. That means:

  • If the tank is already at/above target when a cycle becomes due, the integration does not engage its own heater on top of it. It just watches the sensor and lets the existing heat (from solar diversion, or anything else) accumulate hold-time on its own. Status goes straight to pasteurizing without ever passing through heating, and no geyser_pasteurization_started event fires — only geyser_pasteurization_completed once the hold duration is satisfied, with a heater_engaged: false attribute so you can tell it happened for free.
  • Once the tank crosses target, tracking continues even after whatever heated it switches off. If solar's own controller shuts the element off the moment it reaches target, the water stays hot for a while on thermal mass alone — the integration keeps counting based on the sensor reading until either the hold duration is satisfied, or the temperature actually drops back below target.
  • If a passive hold doesn't quite finish before temperature drops (e.g. the sun goes behind a cloud a few minutes short of the full duration), and the cycle is still due, the integration tops it up with its own heater rather than starting over — the partial hold-time already banked is preserved, not discarded (unless you've enabled strict cycle reset, in which case any drop below target always zeroes the timer, passive or not).
  • This applies independently of the grid power gate. Losing grid power only stops the integration engaging its own heater; it doesn't stop it from recognizing an already-hot tank, since that heat didn't come from the battery in the first place.
  • The integration will never turn off a heater it did not itself turn on. Internally it only ever calls turn_off on the heater entity when it's the one that called turn_on for the current hold — automatically (grid loss, cycle completion, failsafe) or via the Reset/Cancel button/service. A passive/solar-driven hold is only ever watched, never interrupted.
  • Solar heating counts even before a cycle is due, and pushes the due date out. While compliant, a passive hold is tracked just like a due one: status shows pasteurizing, cycle progress climbs, and when it completes, last_pasteurization updates and the due date moves out under the early-completion rule. If solar pasteurizes the tank regularly, the integration may never need to run its own heater.
  • Each heating episode counts once. After a completion, the tank must cool below target before another passive hold can start. A tank that stays hot after completing stays compliant; it won't complete again and re-fire geyser_pasteurization_completed every 32 minutes. After a Home Assistant restart, a tank that's already hot also waits for the next cool-down, since the integration can't know whether that hold already counted.
  • An early passive hold that falls short is discarded, not banked. If the temperature drops below target before an early, not-yet-due hold completes, its partial progress is dropped. Partial progress is only kept across dips once a cycle is due (see the top-up behavior above).

In short: an active cycle (heater engaged by this integration) only ever happens for the portion of the required duration that ambient/solar heating hasn't already covered, and each heating episode is counted at most once.

How it works — the state machine

 COMPLIANT ──(window elapsed)──▶ DUE ──(temp < target: window ok / manual trigger)──▶ HEATING
     ▲  ▲                          │  │                                                  │
     │  │                          │  └──(temp ≥ target, any time)──▶ PASTEURIZING ◀──────┘
     │  │                          │                                       │      (temp ≥ target)
     │  └──(temp ≥ target, any time, no window needed)────────────────────►│
     │                                                                     │
     └──────────────────────(hold duration reached)──────────────────────┘
                                                                            │
                                                            (temp < target, non-strict: keep banked time)
                                                                            ▼
                                                                         HEATING / DUE
                                                                            │
                                                         (heater-engaged runtime ≥ max failsafe)
                                                                            ▼
                                                                         FAILED (manual reset required)
  • Compliant — a valid hold completed within the rolling window (whether driven by the integration's own heater, passively, or a mix of both). If the tank cools below target and is later heated back above it, for example by solar, it moves to pasteurizing. Completing that hold early moves the due date out.
  • Due — the window has elapsed with no valid hold recorded, and the tank is currently below target. If on grid power and (no allowed-run-window is configured, or the current time is inside it), the integration's own heater engages; otherwise it waits — including waiting on ambient/solar heating to bring it up on its own.
  • Heating — this integration's heater is engaged, temperature rising toward target.
  • Pasteurizing — temperature is at/above target right now, however that happened; the hold-duration timer is counting. If temperature drops below target before completion, the timer either pauses (default) or resets to zero (strict mode), falling back to heating (if the integration's heater is engaged) or due (if not, e.g. it was a passive hold). An early passive hold, started while still compliant, instead returns to compliant and its partial progress is discarded.
  • Failed — the integration's own heater ran for the configured maximum failsafe time without completing a hold (time spent passively at temperature, or paused for grid power, never counts toward this). The heater is disengaged immediately and the state stays Failed until you acknowledge it (Reset or Cancel).

Entities

Every entity is grouped under a single Geyser Pasteurization device.

Entity Type Description
sensor.geyser_pasteurization_status Sensor (enum) Current state: compliant, due, heating, pasteurizing, failed. pasteurizing can be reached without heating if the tank is already hot passively (e.g. from solar) — see Passive / solar-driven pasteurization.
sensor.geyser_last_pasteurization Sensor (timestamp) When the last successful cycle actually completed
sensor.geyser_pasteurization_next_due Sensor (timestamp) The fixed, drift-free schedule point at which the next cycle becomes due — see Fixed due schedule
sensor.geyser_days_since_pasteurization Sensor Days elapsed since the last successful cycle
sensor.geyser_cycle_progress Sensor 0–100% progress of an active hold; attributes include minutes elapsed/remaining
binary_sensor.geyser_pasteurization_overdue Binary sensor on when the rolling window has been exceeded
binary_sensor.geyser_pasteurization_active Binary sensor on while heating or pasteurizing
binary_sensor.geyser_on_grid_power Binary sensor on while on grid power. Only created if a grid power sensor is configured.
button.trigger_pasteurization_cycle Button Immediately starts a cycle, bypassing the allowed run window (but not the grid power gate, if configured)
button.reset_pasteurization_timer Button Marks the system as pasteurized now (e.g. you verified disinfection some other way), without running a cycle
button.cancel_pasteurization_cycle Button Safely aborts an in-progress cycle (heater off) without marking it compliant

Services

Service Description Fields
geyser_pasteurization.manual_pasteurization_trigger Immediately starts a disinfection cycle device_id or entry_id (optional if you only have one instance configured)
geyser_pasteurization.reset_timer Marks the system as pasteurized now, without running a cycle device_id or entry_id
geyser_pasteurization.cancel_pasteurization_cycle Aborts an in-progress cycle device_id or entry_id

Example:

service: geyser_pasteurization.manual_pasteurization_trigger
data:
  device_id: <your device id>

Events

Listen for these in automations to hook up mobile notifications, dashboards, or logbook entries:

Event Fired when Data
geyser_pasteurization_started The integration engages its own heater (never fires for a purely passive/solar hold) entry_id, target_temperature, required_duration_minutes, hold_points (the active time–temperature table), banked_hold_seconds and banked_progress_percent (any passive hold already accumulated before engaging)
geyser_pasteurization_completed A hold at/above target reaches 100% progress per the hold table entry_id, completed_at, duration_seconds (actual time spent at/above target), heater_engaged (false if fully passive/solar-driven), next_due_at (the newly advanced fixed schedule point)
geyser_pasteurization_failed The integration's own heater-engaged runtime exceeds the failsafe without completing entry_id, reason, failed_at

Example automation — notify on failure:

automation:
  - alias: Notify on failed pasteurization cycle
    trigger:
      - platform: event
        event_type: geyser_pasteurization_failed
    action:
      - service: notify.mobile_app_your_phone
        data:
          title: "Geyser disinfection failed"
          message: "{{ trigger.event.data.reason }}"

Dashboard example

type: entities
title: Geyser Pasteurization
entities:
  - entity: sensor.geyser_pasteurization_status
  - entity: sensor.geyser_cycle_progress
  - entity: sensor.geyser_days_since_pasteurization
  - entity: sensor.geyser_last_pasteurization
  - entity: sensor.geyser_pasteurization_next_due
  - entity: binary_sensor.geyser_pasteurization_overdue
  - entity: button.trigger_pasteurization_cycle
  - entity: button.reset_pasteurization_timer
  - entity: button.cancel_pasteurization_cycle

Safety notes

  • The heater is only ever commanded via turn_on/turn_off on the domain you configured (switch, input_boolean, climate, or water_heater). Make sure that entity actually controls the electric element you intend to pasteurize with — this integration has no independent way to verify that.
  • The failsafe run-time cutoff is a hard ceiling; if you have a geyser that's very slow to heat, raise it rather than relying on default 180 minutes.
  • A Home Assistant restart never resumes an in-progress cycle automatically — after a restart the integration only recomputes whether you're compliant or due from the last persisted successful-cycle timestamp, and will only start a new cycle through the normal due/allowed-window/manual-trigger logic.
  • A failed state requires a manual Reset or Cancel — it will not silently retry.

Troubleshooting

  • Status stuck on due, never starts heating — check whether an allowed run window or grid power gate is configured and currently blocking it; either wait, adjust the window, or use the manual trigger button/service. Also check whether the tank is already at/above target — if so, this is expected: it's waiting on the passive hold to finish rather than engaging its own heater (see Passive / solar-driven pasteurization).
  • Temperature sensor unavailable/unknown — the integration logs a warning and pauses timer accumulation (it does not turn the heater off) until the sensor reports a valid numeric value again.
  • Heater entity doesn't respond — confirm its domain is one of switch, input_boolean, climate, water_heater, and that the entity actually accepts turn_on/turn_off.