Section setpoints were only sent when AOG's PGN 229 demand changed. Whenever it did not change, an implement in automatic mode ran on its own state: - After switching to automatic, nothing was sent until a section changed. AOG turns its own Auto button off on every field open/close, so after a field change its demand stays all off and the TC sent nothing at all. In the field a spreader in automatic spread full width for 17 and 47 minutes without receiving a single setpoint. - When the implement's master switch went on, it was not told the current setpoint. - When AOG stopped sending PGN 229 (field closed), the last demand stayed in force, even with sections on. Now the TC keeps AOG's latest demand (all off once PGN 229 stops for 2 s), keeps client setpoints current in manual mode too, and sends every section setpoint plus Setpoint Work State right after section control is enabled, after the implement reports automatic, after an implement master work state goes on, and every 2 s while in automatic. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
gunicsba
marked this pull request as draft
October 14, 2026 16:01
This was referenced Nov 8, 2026
gunicsba
added a commit
that referenced
this pull request
Nov 11, 2026
…tting is off - After section control is switched on (connect, field open, PGN 241), send every condensed setpoint block and DDI 289, forced, from AOG's current demand (all off when none arrived in the last 2 s). Change-only sends never told the implement "all off" when AOG's Auto was off, so it kept running on its own state (ISO 11783-10 F.3.5.3 b). - With sectionControlOnConnect off, schedule nothing on connect. Before, DDI 160 = 0 went out on every connect, and after one SC press or field open every later connect switched on. Helpers match #106 (send_all_section_setpoint_states, forceWorkState) so the two merge cleanly. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
gunicsba
added a commit
that referenced
this pull request
Nov 11, 2026
) * Switch section control on automatically when an implement connects Until now an implement stayed in manual mode after connecting until the operator pressed AOG's ISOBUS SC button, which sends PGN 241. The TC now remembers the section control state it wants and applies it to each client 2 s after its pool is activated: it sets the local auto flag and writes DDI 160 when the implement declares it. The initial state comes from the new settings.json key "sectionControlOnConnect" (default true). Pressing AOG's button still switches all clients and also becomes the state for implements that connect later. The implement can still decline or go back to manual; its DDI 160 report is followed as before. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * Switch section control on when AOG opens a field New sectionControlOnFieldOpen setting (default on): when AOG opens a field, the TC switches section control on as if AOG's SC button was pressed (the same update_section_control_enabled(true) that PGN 241 "enabled" triggers). AOG sends the field name (PGN 0xF3) on every field open and close, and again when the TC reconnects. Older AOG versions do not, so PGN 229 starting after a 2 s gap (AOG sends it only while a field is open) counts as a field opening too. Both report the same opening, so it is acted on at most once per 5 s. Field open and close are logged. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * Keep the field name branch where the guidance track code adds its own PR #84 also adds a PGN 0xF3 branch to this if/else chain, between 0xF1 and 0xF2. In different places, the two merge without a conflict and the second never runs. In the same place, Git reports the conflict. No behaviour change. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * Only a new field name counts as a field opening once AOG sends one A gap of more than 2 s in PGN 229 (AOG stalling, lost UDP packets) was treated as a field opening and switched section control back on, even when the operator had switched it off and the same field stayed open. Once AOG has sent a field name (PGN 0xF3), only a change of field name switches section control on; the PGN 229 fallback stays for AOG versions that do not send the field name. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * Send the full setpoint on enable; send nothing on connect when the setting is off - After section control is switched on (connect, field open, PGN 241), send every condensed setpoint block and DDI 289, forced, from AOG's current demand (all off when none arrived in the last 2 s). Change-only sends never told the implement "all off" when AOG's Auto was off, so it kept running on its own state (ISO 11783-10 F.3.5.3 b). - With sectionControlOnConnect off, schedule nothing on connect. Before, DDI 160 = 0 went out on every connect, and after one SC press or field open every later connect switched on. Helpers match #106 (send_all_section_setpoint_states, forceWorkState) so the two merge cleanly. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> --------- Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
Summary
Section setpoints were only sent when AOG's PGN 229 demand changed. When it didn't change, an implement in automatic ran on its own state. In a field log from 2026-10-13, a Sulky Isolink spreader in automatic spread full width for 17 and 47 minutes without receiving a single setpoint. The operator reported it as "the implement doesn't respond to commands", but no commands were being sent.
How it happens: AOG turns its own section Auto button off on every field open/close (
JobNew()/JobClose()). The ISOBUS SC button keeps showing green, because it reflects the TC heartbeat. So after a field change, AOG's demand stays all off, the TC never sends anything, and the spreader switches all 12 sections on when its master switch goes on. AOG draws coverage from the implement's reported sections, so the map looks normal.Two related gaps:
Changes
MyTCServerkeeps AOG's latest demand and treats no PGN 229 for 2 s as all off. It logs both transitions.SECTION_SETPOINT_REFRESH_MS).Behaviour change
With section control enabled but AOG asking for no sections (Auto off, or no field open), the implement is now told off and stops working. Before, it ran on its own state. Over-application becomes under-application, which the operator notices immediately. The section demand diagnostics PR adds a log line and an AOG message that explain why.
Notes
Application::update(). Keep both sides; the resolution is intest/szello-debug.Testing