Data Types and UDT Support

Supported Data Types

Type Size Description JSON Type
BOOL 1 bit Boolean true/false
SINT 1 byte 8-bit signed integer number
USINT/BYTE 1 byte 8-bit unsigned integer number
INT 2 bytes 16-bit signed integer number
UINT/WORD 2 bytes 16-bit unsigned integer number
DINT 4 bytes 32-bit signed integer number
UDINT/DWORD 4 bytes 32-bit unsigned integer number
LINT 8 bytes 64-bit signed integer number
ULINT/LWORD 8 bytes 64-bit unsigned integer number
REAL 4 bytes 32-bit float number
LREAL 8 bytes 64-bit float number
STRING Variable Text string string

Arrays

Arrays of known types are published as JSON arrays:

{
  "tag": "Temperatures",
  "value": [72.5, 73.1, 71.8, 72.0],
  "type": "REAL[4]"
}

Multi-dimensional arrays are flattened to a single dimension.

Writing Values

WarLink supports writing values to PLC tags through the Browser tab. Press W on any writable tag to open the write dialog.

Type-Aware Writes

When writing to a tag, WarLink uses the tag's actual data type discovered from the PLC. This ensures the correct CIP type code is sent, preventing type mismatch errors.

Scalar Value Formats

Type Format Examples
BOOL true or false (case-insensitive) true, FALSE, True
Integer types Decimal number 42, -100, 65535
REAL/LREAL Decimal with optional fraction 3.14, -0.5, 100.0
STRING Plain text (no quotes needed) Hello World

Array Value Formats

Arrays are written using bracket notation with space-separated or comma-separated values:

[value1 value2 value3]
[value1, value2, value3]

Examples:

Type Write Format
DINT[5] [1 2 3 4 5] or [1, 2, 3, 4, 5]
BOOL[4] [true false true false]
REAL[3] [1.5 2.5 3.5]
STRING[3] [one two three]

Quoted Strings in Arrays

For string arrays containing spaces, use double quotes around each element:

["one dog" "two dogs" "three dogs"]

You can mix quoted and unquoted strings:

["hello world" simple "another phrase" test]

Note: Quotes are only needed when string elements contain spaces. Simple strings work without quotes.

Byte Order

Different PLC families use different byte orders:

PLC Family Protocol Byte Order
Siemens S7 S7comm Big-endian
Omron FINS FINS TCP/UDP Big-endian
Omron EIP EtherNet/IP (CIP) Little-endian
Allen-Bradley Logix EtherNet/IP (CIP) Little-endian
Allen-Bradley PCCC (SLC-500/PLC-5/MicroLogix) PCCC over EtherNet/IP Little-endian
Beckhoff TwinCAT ADS Little-endian

Note: Omron NJ/NX series using EtherNet/IP (CIP) are little-endian, matching Allen-Bradley. Older Omron PLCs using FINS are big-endian.

Known types are automatically converted - you'll see the same numeric value regardless of PLC family.

Unknown types (UDTs without templates, raw structures) are returned as byte arrays in the PLC's native order:

{
  "tag": "UnknownStruct",
  "value": [120, 86, 52, 18],
  "type": "Unknown"
}

To decode manually:

  • Big-endian (S7/Omron): Most significant byte first
  • Little-endian (Logix/Beckhoff): Least significant byte first

UDT/Structure Support

WarLink automatically unpacks UDT (User-Defined Type) members when the template is known on supported PLCs. You can publish the entire UDT as a JSON object, or publish individual members separately using dot-notation.

PLC Structure:

MachineStatus (UDT)
├── Running: BOOL
├── Speed: REAL
├── Counter: DINT
└── Timestamp: LINT

Publishing Entire UDT as JSON Object

When you enable a UDT tag (e.g., MachineStatus), it is published as a nested JSON object:

{
  "tag": "MachineStatus",
  "value": {
    "Running": true,
    "Speed": 1500.5,
    "Counter": 42,
    "Timestamp": 1705312200000
  },
  "type": "UDT",
  "timestamp": "2024-01-15T10:30:00Z"
}

Nested UDTs are recursively unpacked into nested JSON objects.

Publishing Individual Members

You can also enable individual UDT members using dot-notation in the Tag Browser. Each member is published as a separate tag:

  • MachineStatus.Running = true
  • MachineStatus.Speed = 1500.5
  • MachineStatus.Counter = 42
  • MachineStatus.Timestamp = 1705312200000

This is useful when you only need specific members or want finer control over change detection.

Change Detection Filtering

UDTs often contain volatile members (timestamps, heartbeats, counters) that change frequently but aren't meaningful for data capture. You can exclude these from change detection.

Via Tag Browser

Press i on a UDT member to toggle ignore status. Ignored members show [I] indicator. You can also set ignore_changes in the tag configuration.

Auto-Detection

When you enable a UDT tag, WarLink automatically ignores common volatile types:

  • TIMER, COUNTER
  • TIME, LTIME
  • DATE, DATE_AND_TIME
  • TIME_OF_DAY, TOD, DT

How It Works

  • Ignored members are still published - they appear in the payload with current values
  • They don't trigger republishing - if only ignored members change, no message is sent
  • Non-ignored changes trigger full publish - the entire UDT (including ignored members) is republished

Example: A UDT with Temperature (not ignored) and Timestamp (ignored):

  • Temperature changes from 72.0 to 72.5 → Message published with both values
  • Only Timestamp changes → No message published
  • Both change → Message published with both values

Manual Tags (S7/Omron FINS/PCCC)

For PLCs without automatic discovery, add tags manually in the Browser tab (press a). Specify the address and data type when prompted.

S7 Addressing

Format Example Description
DB<n>.<offset> DB1.0 Data block at byte offset
DB<n>.<offset>.<bit> DB1.4.0 Bit within data block
DB<n>.<offset>[count] DB1.0[10] Array
I<offset> I0 Input
Q<offset> Q0 Output
M<offset> M0 Marker

Omron Addressing

Area Format Example
Data Memory DM<addr> DM100
Core I/O CIO<addr> CIO50
Work Area WR<addr> WR10
Holding HR<addr> HR0
Auxiliary AR<addr> AR0

Bit access: DM100.5 (bit 5) Arrays: DM100[10] (10 words)

PCCC Addressing (SLC-500/PLC-5/MicroLogix) — Experimental

File Type Format Example
Integer N<file>:<element> N7:0
Float F<file>:<element> F8:5
Binary B<file>:<element> B3:0
Timer T<file>:<element> T4:0
Counter C<file>:<element> C5:0
Control R<file>:<element> R6:0
String ST<file>:<element> ST9:0
Long L<file>:<element> L10:0

Sub-elements: T4:0.ACC (timer accumulated), T4:0.PRE (timer preset), C5:0.ACC

Tag Aliases

For address-based PLCs (S7, Omron FINS, SLC-500/PLC-5/MicroLogix), aliases give friendly names to memory addresses. When adding a manual tag, set an alias in the edit dialog. The alias appears in all published messages instead of the raw address.