From ee156c330fe59ade7d764e0be788f99695813751 Mon Sep 17 00:00:00 2001 From: Trevor Sodorff Date: Thu, 26 Mar 2026 12:12:34 -0700 Subject: [PATCH] Update telemetry_fields.yaml Update for enhanced site control --- .../resources/fields/telemetry_fields.yaml | 27 +++++++++++++++++++ 1 file changed, 27 insertions(+) diff --git a/ontology/yaml/resources/fields/telemetry_fields.yaml b/ontology/yaml/resources/fields/telemetry_fields.yaml index d673a78de..f6a16a07f 100644 --- a/ontology/yaml/resources/fields/telemetry_fields.yaml +++ b/ontology/yaml/resources/fields/telemetry_fields.yaml @@ -415,6 +415,12 @@ literals: - compressor_current_sensor: fixed_min: 0.0 flexible_max: 100.0 +- local_override_compressor_alarm: + - ACTIVE + - INACTIVE +- local_override_supply_fan_alarm: + - ACTIVE + - INACTIVE - compressor_lost_power_alarm: - ACTIVE - INACTIVE @@ -978,6 +984,9 @@ literals: - emergency_alarm: - ACTIVE - INACTIVE +- emergency_stop_alarm: + - ACTIVE + - INACTIVE - emergency_battery_status: - ON - OFF @@ -1942,6 +1951,9 @@ literals: - high_heating_supply_water_temperature_alarm: - ACTIVE - INACTIVE +- high_gas_pressure_alarm: # For natural gas specifically + - ACTIVE + - INACTIVE - high_leaving_air_preheating_coil_temperature_alarm: - ACTIVE - INACTIVE @@ -2346,6 +2358,9 @@ literals: - local_override_isolation_valve_alarm: - ACTIVE - INACTIVE +- local_override_discharge_air_isolation_damper_alarm: + - ACTIVE + - INACTIVE - loop_chilled_water_differential_pressure_sensor: flexible_min: -34473.78945 flexible_max: 344737.8945 @@ -2424,6 +2439,9 @@ literals: - low_flowrate_alarm: - ACTIVE - INACTIVE +- low_gas_pressure_alarm: # For natural gas specifically + - ACTIVE + - INACTIVE - low_heating_supply_water_temperature_alarm: - ACTIVE - INACTIVE @@ -2762,6 +2780,9 @@ literals: - north_wind_linearvelocity_sensor: flexible_min: 0.0 flexible_max: 44.704 +- occupancy_status: + - OCCUPIED + - UNOCCUPIED - oil_differential_pressure_sensor: flexible_min: 0.0 flexible_max: 1034214.0 @@ -4365,6 +4386,9 @@ literals: - zone_air_occupied_heating_temperature_setpoint: flexible_min: 255.9259259 flexible_max: 308.1481481 +- zone_air_occupied_cooling_temperature_setpoint: + flexible_min: 290 + flexible_max: 305 - zone_air_offset_temperature_setpoint: flexible_min: 254.8148148 flexible_max: 283.1481481 @@ -4461,6 +4485,9 @@ literals: - zone_air_unoccupied_heating_temperature_setpoint: flexible_min: 255.9259259 flexible_max: 308.1481481 +- zone_air_unoccupied_cooling_temperature_setpoint: + flexible_min: 255.9259259 + flexible_max: 308.1481481 - zone_air_voc_aqi_sensor: fixed_min: 0 flexible_max: 500